Eaton xEnergy Safety Ci LV systems LV switchgear. Insulated enclosure, top+bottom open, HxWxD=250x375x225mm
| Product Name |
Eaton xEnergy Safety Ci empty enclosure insulated
|
| Catalog Number |
027019
|
| Product Length/Depth |
225 mm
|
| Product Height |
250 mm
|
| Product Width |
375 mm
|
| Product Weight |
2.203 kg
|
| Compliances |
RoHS conform
|
| Certifications |
EN 62208
EN 61439-2 |
| Special features |
Housing prepared for distribution board
Two sides closed, can be folded out
two sides open
Sealable cover fasteners
Integrated pressure-relief mechanism for short-circuits
|
| Type |
Basic enclosure
Panel enclosures
xEnergy Safety Ci
|
| Features |
UV resistance beneath protective shield
Cover with overpressure release |
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
Meets the product standard's requirements.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Lower part: 960 °C / cover: 850 °C
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
| 10.2.5 Lifting |
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
|
| 10.2.6 Mechanical impact |
IK10
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
IP65
|
| 10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
| 10.5 Protection against electric shock |
Protection class 2, therefore not applicable.
|
| 10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Ui = 1000 V AC
|
| 10.9.3 Impulse withstand voltage |
8 kV
|
| 10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
| Surface finishing |
Resistant to corrosion
|
| Degree of protection |
IP65
Other IK10 |
| Enclosure material |
Plastic
|
| Surface protection |
Other
|
| Chemical resistance |
Resistant against: acids < 10 %, mineral oil, alcohol, gasoline, greases, salt solutions
Partly resistant to: Acids > 10 % Not resistant to: alkalis, benzene |
| Circuit integrity |
Other
|
| Unit type |
Single unit
|
| Built-in depth |
200 mm
|
| Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) |
25 W
|
| Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) |
22 W
|
| Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) |
24 W
|
| Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) |
51 W
|
| Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) |
45 W
|
| Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) |
48 W
|
| Color |
Gray
|
| Cover/door color |
Transparent
|
| Cover/door model |
Closed
|
| Cover/door type |
Transparent
None Optional |
| Number of openings (flange plates) |
4
|
| Plate thickness (cabinet) |
6 mm
|
| Plate thickness (cover/door) |
6 mm
|
| RAL-number |
7035
|
| Width in number of modular spacings |
15
|
| Ambient operating temperature details |
-40 °C - 80 °C
|
| Material |
Non-reinforced polycarbonate (cover)
Halogen free Glass-fibre reinforced polycarbonate (base) |
| Mounting method |
Surface mounted (plaster)
|
| Number of rows |
0
|
| Functions |
Extension possible
|
| Temperature resistance |
Temperature resistant: 80 °C (gasket)
Temperature resistant: -40 °C - 120 °C (enclosure) Temperature resistant: 85 °C (enclosure bolt) |
| Flammability characteristics (UL) |
V1 (base) (UL94)
V2 (cover) (UL94) |
| Protection class |
II
|
| Number of modules |
1
|
| Surface treatment |
Resistant to corrosion
|
| Internal depth |
200 mm
|
| Mounting depth with mounting plate |
200 mm
|
| Nominal current |
1600 A
|
| Number of conduit inlets |
76
|
| Suitable for |
Lightning protection
Outdoor use |
| Saline spray resistance |
IEC 60068-2-11
|
| Enclosure material quality |
Other
|
| Type of coating |
Other
|