照片为代表
                                
                                
                                    
                                    Download
                                
                                
                                Eaton Moeller® series U-PKZ0 Undervoltage release PKZ0(4), PKE, AC, 240 V 50 Hz, Screw terminals
| Product Name | 
                                                Eaton Moeller® series U-PKZ0 Accessory Undervoltage Release
                                             | 
| Catalog Number | 
                                                073136
                                             | 
| Product Length/Depth | 
                                                68 mm
                                             | 
| Product Height | 
                                                90 mm
                                             | 
| Product Width | 
                                                24 mm
                                             | 
| Product Weight | 
                                                0.126 kg
                                             | 
| Certifications | 
                                                CSA-C22.2 No. 14  UL CSA CSA File No.: 165628 IEC/EN 60947-4-1 UL File No.: E36332 UL 508 CE CSA Class No.: 3211-05 UL Category Control No.: NLRV | 
| Used with | 
                                                Motor protective circuit-breaker
                                             | 
| Suitable as | 
                                                EMERGENCY STOP or EMERGENCY switching-off device in accordance with IEC/EN 60204 when combined with circuit breaker
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| Electric connection type | 
                                                Screw connection
                                             | 
| Rated control supply voltage (Us) at DC - max | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at DC - min | 
                                                0 V
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                0 A
                                             | 
| Rated operational voltage (Ue) at AC - max | 
                                                480 V
                                             | 
| Rated operational voltage (Ue) at AC - min | 
                                                42 V
                                             | 
| Rated operational voltage (Ue) at DC - max | 
                                                250 V
                                             | 
| Rated operational voltage (Ue) at DC - min | 
                                                24 V
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                0.5 W
                                             | 
| Product category | 
                                                Accessories
                                             | 
| Ambient operating temperature - max | 
                                                55 °C
                                             | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                0 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Number of contacts (change-over contacts) | 
                                                0
                                             | 
| Number of contacts (normally closed contacts) | 
                                                0
                                             | 
| Number of contacts (normally open contacts) | 
                                                0
                                             | 
| Rated control supply voltage (Us) at AC, 50 Hz - max | 
                                                240 V
                                             | 
| Rated control supply voltage (Us) at AC, 50 Hz - min | 
                                                240 V
                                             | 
| Rated control supply voltage (Us) at AC, 60 Hz - max | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 60 Hz - min | 
                                                0 V
                                             | 
| Voltage type | 
                                                AC
                                             | 
| Mounting position | 
                                                Can be fitted to left side of the motor protection switch
                                             | 
| Suitable for | 
                                                Motor safety switch
                                             | 
| Drop-out voltage | 
                                                0,7- 0,35 x Uc
                                             | 
| Power consumption, pick-up, 50 Hz | 
                                                5 VA, Pull-in power, Coil in a cold state and 1.0 x Us
                                             | 
| Power consumption, pick-up, 60 Hz | 
                                                5 VA, Pull-in power, Coil in a cold state and 1.0 x Us
                                             | 
| Power consumption, sealing, 50 Hz | 
                                                3 VA, Coil in a cold state and 1.0 x Us
                                             | 
| Power consumption, sealing, 60 Hz | 
                                                3 VA, Coil in a cold state and 1.0 x Us
                                             | 
| Pick-up voltage | 
                                                0.85 - 1.1 V x Uc
                                             | 
| Terminal capacity (solid/flexible with ferrule) | 
                                                2 x (0.75 - 2.5) mm²  1 x (0.75 - 2.5) mm² | 
| Terminal capacity (solid/stranded AWG) | 
                                                2 x (18 - 14)  1 x (18 - 14) |