Eaton xEnergy Safety Ci LV systems LV switchgear. Panel enclosure, with gland plate and cable glands, HxWxD=750x375x225mm
Product Name |
Eaton xEnergy Safety Ci empty enclosure insulated
|
Catalog Number |
098250
|
Product Length/Depth |
225 mm
|
Product Height |
750 mm
|
Product Width |
375 mm
|
Product Weight |
6.255 kg
|
Compliances |
IEC/EN 60439-1, VDE 0660 Part 500
RoHS conform |
Certifications |
EN 61439-2
EN 62208 |
Used with |
The reference values indicated in the table apply to the basic elements of the distribution board. As far as devices, terminals etc. fitted into the enclosures are concerned, their own specific technical data and rated values apply.
|
Special features |
Low-voltage fuses (IEC/EN 60269, VDE 0636)
Sealable cover fasteners
Sides closed, but with full area knockout
Open top
Fitting of cable supports in the distribution board with wedge-lock fastener
Gland plate can be split, cables can be inserted from the front
|
Type |
Basic enclosure
Panel enclosure with gland plates fitted
xEnergy Safety Ci
|
Features |
Cover with overpressure release
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
Meets the product standard's requirements.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Lower part: 960 °C / cover: 850 °C
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
10.2.5 Lifting |
40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
|
10.2.6 Mechanical impact |
IK10
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
IP65
|
10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
10.5 Protection against electric shock |
Protection class 2, therefore not applicable.
|
10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Ui = 1000 V AC
|
10.9.3 Impulse withstand voltage |
8 kV
|
10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
Surface finishing |
Galvanized
Passivated |
Degree of protection |
IK10
IP64 (KST cable entries from above) IP65 (enclosure) IP65 (KST cable entries from below) IP65 Other IP00 (cable entry open) |
Enclosure material |
Plastic
|
Surface protection |
Other
|
Circuit integrity |
Other
|
Unit type |
Stand-alone device
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-5 °C
|
Built-in depth |
200 mm
|
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) |
47 W
|
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) |
40 W
|
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) |
44 W
|
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) |
95 W
|
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) |
81 W
|
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) |
88 W
|
Color |
Light gray (RAL 7035, base)
Transparent, smoky gray (cover) Gray |
Cover/door color |
Transparent
|
Cover/door model |
Closed
|
Cover/door type |
Cover
None |
Number of openings (flange plates) |
6
|
Operating altitude without derating - max |
2000 mm
|
Plate thickness (cabinet) |
6 mm
|
Plate thickness (cover/door) |
6 mm
|
RAL-number |
7035
|
Width in number of modular spacings |
17
|
Cable entry type |
14 - 68 mm (3x)
|
Mounting method |
Surface mounted (plaster)
|
Creepage and clearance distances |
III/3 to IEC/EN 60439-1 (standard)
|
Number of rows |
0
|
Functions |
Extension possible
|
Flammability characteristics of glow rod test |
VDE 0304 Part 3 level IIb, level IIb to IEC 60707
|
Protection class |
II
|
Number of modules |
1
|
Relative humidity |
90 % (at 20 °C)
50 % (at 40 °C) |
Internal depth |
200 mm
|
Mean ambient operating temperature (24 hours) |
35 °C
|
Mounting depth with mounting plate |
200 mm
|
Nominal current |
1600 A
|
Number of conduit inlets |
0
|
Suitable for |
Outdoor use
Lightning protection |
Mounting grid |
25 mm (DIN 43660)
|
Enclosure material quality |
Other
|
Type of coating |
Other
|