| Product Name | 
                                                Eaton Moeller® series BBA Accessory Busbar adapter
                                             | 
| Catalog Number | 
                                                101458
                                             | 
| Product Length/Depth | 
                                                200 mm
                                             | 
| Product Height | 
                                                63 mm
                                             | 
| Product Width | 
                                                72 mm
                                             | 
| Product Weight | 
                                                0.416 kg
                                             | 
| Certifications | 
                                                CSA-C22.2 No. 14  UL File No.: E300273 IEC60439-1 UL 508 UL Category Control No.: NMTR; NMTR7 UL UL 508A CE Certified by UL for use in Canada | 
| Special features | 
                                                Terminal capacity: 10 mm² (AWG 8)
                                             | 
| Type | 
 | 
| Voltage rating (UL CSA 13) | 
                                                600 V AC, UL/CSA
                                             | 
| Adapter width | 
                                                72 mm
                                             | 
| Ambient operating temperature - max | 
                                                55 °C
                                             | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Busbar distance | 
                                                60 mm
                                             | 
| Busbar thickness - max | 
                                                10 mm
                                             | 
| Busbar thickness - min | 
                                                5 mm
                                             | 
| Nominal current | 
                                                63 A
                                             | 
| Number of DIN rails | 
                                                1
                                             | 
| Rail width | 
                                                35 mm
                                             | 
| Voltage rating at AC | 
                                                690 V
                                             | 
| Electric connection type | 
                                                Round conductor
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                0 W
                                             | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                6.9 W
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             | 
| Mounting rail armament | 
                                                1 mounting rail
                                             | 
| Rated operation current (Ie) | 
                                                63 A
                                             |