| Product Name |
Eaton Moeller® series MFD I/O module
|
| Catalog Number |
106045
|
| Product Length/Depth |
44 mm
|
| Product Height |
90 mm
|
| Product Width |
88 mm
|
| Product Weight |
0.12 kg
|
| Certifications |
UL
CSA CSA File No.: 012528 IEC 60068-2-27 CSA-C22.2 No. 142-M1987 EN 61000-6-1/-2/-3/-4 UL Category Control No.: NRAQ UL File No.: E135462 IEC 60068-2-6 UL 508 CE CSA Class No.: 2252-01 + 2258-02 CSA-C22.2 No. 213-M1987 |
| Features |
Measurement value resolution analog/digital depending upon the scaling
Configurable temperature range Additional measurement aids: Filter for the suppression of certain frequencies and their multiples: 50, 60, 250, 500 Hz Input signal, configurable Parallel connection of transistor outputs with resistive load, inductive load with external suppressor circuit, combination within a group - Group 1: Q1 to Q4 Overload and short-circuit protection Input, resistance thermometer Additional measurement aids: Filtering (software), smoothing of analog input signal (PT1 behavior), only with set sampling time, selectable per sensor: yes Analog outputs configurable Output, voltage Input, voltage Measuring principle: Two or three wire per sensor, selectable by connection of sensor |
| Air discharge |
8 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Spring clamp connection
|
| Number of inputs (digital) |
2 (I11, I12, can also be used as analog inputs)
10 2 (can also be used as analog inputs) |
| Operating frequency |
Depending on the suppressor circuit (Inductive load to EN 60947-5-1, With external suppressor circuit, Max. switching frequency, max. duty factor)
40000 Operations/h at resistive load |
| Pollution degree |
2
|
| Accuracy |
1 %, Analog outputs at 25 °C
± 0.8 % of measuring range, Ni1000 sensor (offset error, linearity error, repetition accuracy, temperature error of device included) ± 3 %, of actual value, two MFD devices (Analog Inputs) ± 2 %, of actual value, within a single device (Analog Inputs) 1 %; max. 1.6 % (Pt), 1.2 % (Ni), Analog inputs temperature resistance Pt100 or Ni1000 sensors, two MFD devices between each other (without electromagnetic compatibility) ± 0.8 % of measuring range, Pt100 sensor (offset error, linearity error, repetition accuracy, temperature error of device included) 2 %, Analog outputs at-25 °C - 55 °C |
| Burst impulse |
2 kV, Signal cable, according to IEC/EN 61000-4-4, Level 3
2 kV, Supply cable, according to IEC/EN 61000-4-4, Level 3 |
| Resolution |
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Explosion safety category for dust |
None
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Resolution of the analog inputs |
12 Bit
|
| Resolution of the analog outputs |
12 Bit
|
| Static heat dissipation, non-current-dependent Pvs |
2 W
|
| Supply voltage at DC - max |
24 VDC
|
| Temperature measuring range - max |
400 °C
|
| Temperature measuring range - min |
-40 °C
|
| Environmental conditions |
Condensation: prevent with appropriate measures
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 142 |
| Input |
2 Inputs (Pt100)
Input type resistance sensor: Platinum sensor Pt100 (according to DIN EN 60751, IEC 751: MFD-TP12-PT…) Input type resistance sensor: Nickel sensor Ni1000 (according to DIN 43760: MFD-TP12-NI…) Voltage (DC) |
| Output voltage |
Max. 2.5 V (at signal 0 at external load < 10 MΩ, transistor outputs)
U = Uₑ - 1 V (signal 1 at Iₑ = 0.5 A, transistor outputs) |
| Explosion safety category for gas |
None
|
| Output current |
Max. 0.01 A
|
| Mounting method |
Snap fitting (into the power supply unit)
|
| Screwdriver size |
0.6 x 3.5 mm
|
| Mounting position |
Horizontal
Vertical |
| Output |
Parallel connection of max. 4 Transistor outputs
4 Transistor Outputs Voltage (DC) |
| Contact discharge |
6 kV, according to IEC/EN 61000-4-2, Level 3, ESD
|
| Duty factor |
100 % (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 15 ms, R = 48 Ω, L = 0.24 H)
100 % (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH) 100 % (Inductive load to EN 60947-5-1, Without external suppressor circuit, DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H) 100 % (Inductive load to EN 60947-5-1, With external suppressor circuit) |
| Peak short-circuit current |
16 A
|
| Constant acceleration |
2 g, 57 - 150 Hz, according to IEC/EN 60068-2-6, Vibrations
|
| Constant amplitude |
0,15 mm, 10 - 57 Hz, according to IEC/EN 60068-2-6, Vibrations
|
| Surge rating |
2 kV, Supply cables, symmetrical, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, IEC/EN 61000-4-5, level 2, EMC |
| Potential isolation |
Between Digital inputs 24 V DC: no
Between Analog inputs and PC interface, memory card NET, network, easyLink: yes Between Relay outputs and Power supply: yes Between Analog outputs and Power supply: no Between Analog outputs and Digital outputs: yes Between Analog outputs and PC interface, memory card, NET network, easyLink: yes Between Digital inputs 24 V DC and Outputs: yes Between Analog inputs Pt100 or Ni1000 and PC interface, memory card, easyNet, easyLink: yes Between Analog inputs and Power supply: no Between Analog inputs and Digital inputs: no Between Digital inputs 24 V DC and PC interface, memory card, easyNet, easyLink: yes Between Digital inputs 24 V DC and Power supply: no Between Transistor outputs and Inputs: yes Between Analog outputs and Digital inputs: no Between Transistor outputs and PC interface, memory card, easyNet, easyLink: yes |
| Conversions |
200 - 65535 ms, Analog inputs temperature resistance Pt100 or Ni1000 sensors, with sampling time (adjustable), selectable per sensor
200 ms, Analog inputs temperature resistance Pt100 or Ni1000 sensors, without sampling time Each CPU cycle, Analog outputs Each CPU cycle, Analog inputs |
| Cable length |
10 m, screened, Analog inputs temperature resistance Pt100 or Ni1000 sensors
30 m, screened, Analog inputs 100 m, unscreened, Digital inputs 24 V DC 20 m, screened, Digital inputs 24 V DC |
| Electromagnetic fields |
10 V/m (according to IEC EN 61000-4-3)
|
| Protection against polarity reversal |
Yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
|
| Number of inputs (analog) |
2
2 x Pt-100 or 2 x Ni1000 (temperature resistance sensors) |
| Load resistance |
1 kΩ
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
| Radio interference class |
Class B (EN 55022)
Class B (EN 55011) |
| Pulse characteristics |
Pulse shape of the frequency counter: Square (digital inputs 24 V DC)
|
| Relative humidity |
5 - 95 % (non-condensing)
|
| Residual current |
0.1 mA (on signal "1" per channel)
|
| Rapid counter inputs |
Square (pulse shape)
3 kHz, Counter frequency 4 (I1, I2, I3, I4) |
| Recovery time |
100 µs
|
| Rated operational current (Ie) |
Max. 0.5 A at signal „1” DC per channel
|
| Rated operational voltage |
> 15 V DC (I1 - I4) on 1 signal
24 V DC (digital inputs) 20.4 - 28.8 V DC (Transistor outputs) < 5 V DC (I1 - I4) on 0 signal < 8 V DC (I11, I12) on 0 signal > 8 V DC (I11, I12) on 1 signal 24 V DC |
| Insulation resistance |
According to EN 50178
|
| Degree of protection |
IP20
|
| Delay time |
0.25 ms typ., Digital inputs 24 V DC (I11 - I12), Delay time from 0 to 1, Debounce OFF
0.1 ms typ., Digital inputs 24 V DC (I1 - I4), Delay time from 0 to 1, Debounce OFF 0.2 ms typ., Digital inputs 24 V DC (I11, I12), Delay time from 1 to 0, Debounce OFF 20 ms, Digital inputs 24 V DC, Delay time from 0 to 1, Debounce ON 20 ms, Digital inputs 24 V DC, Delay time from 1 to 0, Debounce ON 0.1 ms typ., Digital inputs 24 V DC (I1 - I4), Delay time from 1 to 0, Debounce OFF |
| Incremental counter |
Pulse shape: Square
Signal offset: 90° Number of counter inputs: 2 (I1 + I2, I3 + I4) Counter frequency: ≤ 3 kHz |
| Signal level |
0 V - 10 V, Signal voltage range, Analog outputs
|
| Short-circuit current |
8 A, Transistor outputs
|
| Input impedance |
11.2 kΩ
|
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Frequency counter |
Counter frequency: 3 kHz (digital inputs 24 V DC)
Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) |
| Short-circuit protection |
Thermal (Q1 - Q4), (evaluation with diagnostics input I16), Transistor outputs
|
| Short-circuit tripping current |
0.7 ≤ Ie ≤ 2 per output, For Ra ≤ 10 mΩ, Transistor outputs
|
| Lamp load |
5 W (without Rv per channel, Q1 - Q4)
|
| Signal range |
0 V, Min. signal range, Analog inputs
10 V, Max. signal range, Analog inputs |
| Functions |
Wire break diagnostic per sensor
Diagnostics upper sensor measuring range exceeded Card diagnostic Diagnostics below lower measurement range Thermal cutout |
| Supply current |
24/44 mA, Normally⁄max., On 1 signal, Transistor outputs
18/32 mA, Normally⁄max., On 0 signal, Transistor outputs |
| Switching frequency |
Max. 1500 Operations (Inductive load to EN 60947-5-1, without external suppressor circuit, DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H, f = 0.5 Hz (max. DF = 50 %))
Max. 1500 Operations (Inductive load to EN 60947-5-1, without external suppressor circuit, T0.95 = 15 ms, R = 48 Ω, L = 0.24 H, f = 0.5 Hz (max. DF = 50 %)) Max. 1500 Operations (Inductive load to EN 60947-5-1, without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH, f = 0.5 Hz (max. DF = 50 %)) |
| Input current |
1 mA (Analog inputs)
< 1.6 mA (Analog inputs temperature resistance Pt100 or Ni1000 sensors) 2.2 mA (Digital inputs, at 24 V DC, at signal 1, I11, I12) |
| Terminal capacity |
0.2 - 2.5 mm² (24 - 12 AWG), flexible with ferrule
0.2 - 4 mm² (24 - 12 AWG), solid |
| Utilization factor |
0.25 (Inductive load to EN 60947-5-1, Without external suppressor circuit, DC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 H)
0.25 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 15 ms, R = 48 Ω, L = 0.24 H) 0.25 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH) 1 (Inductive load to EN 60947-5-1, With external suppressor circuit) |
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
40 °C
|
| Equipment heat dissipation, current-dependent Pvid |
2 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
| Number of outputs (analog) |
1
|