| Product Name |
Eaton Moeller® series LS4 Actuator
|
| Catalog Number |
106860
|
| Product Length/Depth |
10 mm
|
| Product Height |
40 mm
|
| Product Width |
53 mm
|
| Product Weight |
0.022 kg
|
| Certifications |
IEC/EN 60947
|
| Catalog Notes |
With the actuator inserted, the N/O contact is open and the NC contact is closed.
|
| Type |
|
| 10.10 Temperature rise |
Not applicable.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Operating frequency |
1800 Operations/h
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Rated insulation voltage (Ui) |
500 V
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| Mounting position |
As required
|
| Repetition accuracy |
0.02 mm (Contacts/switching capacity)
|
| Shock resistance |
25 g, Standard-action contact, Mechanical, Half-sinusoidal shock 20 ms
|
| Supply frequency |
Max. 400 Hz, Contacts
|
| Model |
Standard actuator
|
| Rated operational current (Ie) |
10 A at AC-15, 24 V
3 A at 24 V 0.8 A at 110 V 0.3 A at 220 V 6 A at AC-15, 220 V 230 V 240 V 4 A at AC-15, 380 V 400 V 415 V |
| Short-circuit protection rating |
Max. 6 A gG/gL, Fuse, Contacts
|
| Terminal capacity (flexible with ferrule) |
2 x (0.5 - 1.5) mm²
1 x (0.5 - 1.5) mm² |
| Terminal capacity (solid) |
2 x (0.75 - 1.5) mm²
1 x (0.75 - 2.5) mm² |