Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Molded Case Switch, 3p, 200A, box terminal
Product Name |
Eaton Moeller series NZM molded case switch
|
Catalog Number |
107579
|
Product Length/Depth |
142 mm
|
Product Height |
185 mm
|
Product Width |
105 mm
|
Product Weight |
2.345 kg
|
Compliances |
RoHS conform
|
Certifications |
UL 489
IEC 60947-2 CSA-C22.2 No. 5-09 UL/CSA CSA certified UL listed UL (File No. E148671) CSA (File No. 22086) CSA (Class No. 4652-06) UL (Category Control Number WJAZ) Specially designed for North America CE marking IEC |
Amperage Rating |
200 A
|
Voltage rating |
690 V - 690 V
|
Circuit breaker frame type |
N2
|
Features |
Protection unit
Motor drive optional |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique Fixed |
Equipment heat dissipation, current-dependent |
38.04 W
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Rated current (Iu) |
250 A
|
Current rating (Iu) (UL 489 csa 22.2 no. 5.1) |
250 A
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Switch positions |
I, +, 0
|
Degree of protection |
In the area of the HMI devices: IP20 (basic protection type)
IP20 |
Direction of incoming supply |
As required
|
Electrical connection type of main circuit |
Frame clamp
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Degree of protection (IP), front side |
IP40 (with insulating surround)
IP66 (with door coupling rotary handle) |
Degree of protection (terminations) |
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal) |
Number of poles |
Three-pole
|
Terminal capacity (copper strip) |
Max. 8 segments of 15.5 mm x 0.8 mm (2x) at terminal box
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched) Min. 2 segments of 9 mm x 0.8 mm at box terminal Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched) NA: max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched) NA: min. 2 segments of 16 mm x 0.8 mm at rear-side connection (punched) Max. 10 segments of 16 mm x 0.8 mm at box terminal |
Lifespan, electrical |
6500 operations at 415 V AC-3
6500 operations at 400 V AC-3 7500 operations at 690 V AC-1 10000 operations at 415 V AC-1 10000 operations at 400 V AC-1 5000 operations at 690 V AC-3 |
Functions |
Disconnectors/main switches
|
Type |
Switch-disconnector
|
Special features |
|
Application |
Branch circuits, feeder circuits
|
Position of connection for main current circuit |
Front side
|
Rated operational current for specified heat dissipation (In) |
200 A
|
Power loss |
30.7 W
|
Short-circuit total breaktime |
< 10 ms
|
Short-circuit release non-delayed setting - max |
2500 A
|
Short-circuit release non-delayed setting - min |
2500 A
|
Terminal capacity (copper busbar) |
M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection Max. 24 mm x 8 mm direct at switch rear-side connection NA: min. 16 mm x 5 mm direct at switch rear-side connection NA: M8 at rear-side screw connection NA: max. 20 mm x 5 mm direct at switch rear-side connection |
Terminal capacity (copper solid conductor/cable) |
10 mm² - 16 mm² (1x) at box terminal
16 mm² (1x) at tunnel terminal 4 mm² - 16 mm² (2x) direct at switch rear-side connection NA: 12 - 6 AWG (1x) direct at switch rear-side connection NA: 12 - 6 AWG (1x) at box terminal NA: 6 AWG (1x) at tunnel terminal 10 mm² - 16 mm² (1x) direct at switch rear-side connection 6 mm² - 16 mm² (2x) at box terminal |
Terminal capacity (aluminum solid conductor/cable) |
10 mm² - 16 mm² (2x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) direct at switch rear-side connection 16 mm² (1x) at tunnel terminal |
Terminal capacity (copper stranded conductor/cable) |
NA: 4 - 350 AWG/kcmil (1x) at 1-hole tunnel terminal
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal NA: 4 - 350 AWG/kcmil (1x) at box terminal 25 mm² - 70 mm² (2x) at box terminal 25 mm² - 185 mm² (1x) at box terminal 25 mm² - 70 mm² (2x) direct at switch rear-side connection 25 mm² - 185 mm² (1x) direct at switch rear-side connection |
Terminal capacity (aluminum stranded conductor/cable) |
25 mm² - 35 mm² (1x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal 25 mm² - 35 mm² (2x) direct at switch rear-side connection |
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
2500 A
|
Instantaneous current setting (Ii) - min |
2500 A
|
Number of operations per hour - max |
120
|
Overload current setting (Ir) - max |
0 A
|
Overload current setting (Ir) - min |
0 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
130 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz |
37.5 kA
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz |
5 kA
|
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz |
330 kA
|
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz |
286 kA
|
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz |
105 kA
|
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz |
53 kA
|
Standard terminals |
Box terminal
|
Optional terminals |
Connection on rear. Screw terminal. Tunnel terminal
|
Rated operating voltage Ue (UL) - max |
600 Y / 347 V
|
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz |
330 kA
|
Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
Rated impulse withstand voltage (Uimp) at main contacts |
8000 V
|
Rated insulation voltage (Ui) |
1000 V AC
|