照片为代表
Download
Eaton xEffect xVtl Enclosures Switch- & Controlgear Enclosure. Distribution cabinet, HxWxD=2000x600x500mm, IP40
Product Name |
Eaton xEffect xVtl empty enclosure
|
Catalog Number |
114422
|
Product Length/Depth |
500 mm
|
Product Height |
2015 mm
|
Product Width |
600 mm
|
Product Weight |
65.2 kg
|
Compliances |
RoHS conform
|
Features |
EMC-version
Mounting plate depth-adjustable Connectable |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
Meets the product standard's requirements.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Not applicable.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Not applicable.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
10.2.5 Lifting |
Met; assembled and secured as per the latest applicable instruction leaflet.
|
10.2.6 Mechanical impact |
IK10
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
IP40
|
10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
10.5 Protection against electric shock |
< 0.1 Ω; meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Ui = 690 V AC
|
10.9.3 Impulse withstand voltage |
6 kV
|
10.9.4 Testing of enclosures made of insulating material |
Does not apply to metal enclosures.
|
Fitted with: |
Mounting plate
|
Pollution degree |
3
|
Surface finishing |
Powder coating
|
Degree of protection |
IP40
IK10 4X (NEMA) |
Heat diss. ambient 35°C delta T:20°C free stand individ. encl. top (IEC 60890) |
218 W
|
Heat diss. ambient 35°C delta T: 20°C free stand middle encl. top (IEC 60890) |
194 W
|
Heat diss. ambient 35°C delta T:20°C free stand starting encl. top (IEC 60890) |
205 W
|
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) |
205 W
|
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) |
172 W
|
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) |
196 W
|
Heat diss. ambient 35°C delta T:35°C free stand individ. encl. top (IEC 60890) |
437 W
|
Heat diss. ambient 35°C delta T: 35°C free stand middle encl. top (IEC 60890) |
389 W
|
Heat diss. ambient 35°C delta T:35°C free stand starting encl. top (IEC 60890) |
411 W
|
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) |
412 W
|
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) |
346 W
|
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) |
393 W
|
Material quality |
Other
|
Color |
Gray
|
Permissible load of the mounting plate according to IEC 62208 - max |
4000 N
|
Number of locks |
1
|
RAL-number |
7035
|
Material |
Steel
|
Mounting method |
Wall fastening
|
Overvoltage category |
IV
|
Installation type |
Floor standing wall model
|
Protection class |
I
|
Number of covers/doors |
1
|
Suitable for |
Metrical mounting
|
Permissible load of the enclosure according to IEC 62208 - max |
5000 N
|
Permissible load of the door(s) according to IEC 62208 - max |
1000 N
|
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890 |
412.035 W
|
Number of connector holes |
0
|