Eaton Moeller® series DIL-SWD Function element, contactor, SmartWire-DT, DIL/MSC
| Product Name |
Eaton Moeller® series DIL-SWD SWD contactor module
|
| Catalog Number |
118560
|
| Product Length/Depth |
72 mm
|
| Product Height |
38 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.04 kg
|
| Certifications |
CSA File No.: 2324643
CSA Class No.: 3211-07 CSA-C22.2 No. 14-05 UL UL File No.: E29184 CSA IEC/EN 61131-2 UL Category Control No.: NKCR CE EN 50178 IEC/EN 60947 IEC/EN 60947-4-1 UL 508 |
| Type |
SWD contactor modules
|
| Features |
Fieldbus connection over separate bus coupler possible
|
| Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Spring clamp connection
|
| Fitted with: |
Own supply
|
| Number of inputs (digital) |
2
|
| Pollution degree |
2
|
| Burst impulse |
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 |
| Addressing |
Address set automatically
|
| Connection to SmartWire-DT |
Yes
|
| Category (EN 954-1) |
1
|
| Explosion safety category for dust |
None
|
| Environmental conditions |
Condensation: prevent with appropriate measures
|
| Explosion safety category for gas |
None
|
| Output current |
0.5 A
|
| Current consumption |
40 mA, SmartWire-DT network
|
| Voltage type |
DC
|
| Mounting position |
As DILM7 to DILM38
|
| Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
| Overvoltage category |
II
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
30 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
0.3 m
|
| Input current at signal 1 |
3 mA
|
| Number of auxiliary contacts |
2
|
| Number of HW-interfaces (industrial ethernet) |
0
|
| Number of HW-interfaces (other) |
1
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Constant acceleration |
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
| Constant amplitude |
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
|
| Potential isolation |
Connection auxiliary contact: no
|
| Cable length |
≤ 2.8 m, Connection auxiliary contact
|
| Electromagnetic fields |
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) |
| Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Protocol |
Other bus systems
|
| Radio interference class |
Class A (EN 55011)
|
| Number of outputs (digital) |
1
|
| Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
| Pick-up current |
500 mA (for DILM 17-38)
188 mA (for DILM 12-15) 125 mA (for DILM 7-9) |
| Connection type |
Push in terminals, Auxiliary contact
SWD: Plug, 8-pole External device plug SWD4-8SF2-5, SmartWire-DT |
| Data transmission type |
None
|
| Rated operational voltage |
15 V DC (auxiliary contact)
|
| Degree of protection |
IP20
|
| Station |
SmartWire-DT slave, SmartWire-DT network
|
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
| Functions |
Contactor actuation
Display of Switch status Contactor, status of the digital inputs 1 and 2 For connecting the contactors to SmartWire-DT |
| System accessory |
Yes
|
| Terminal capacity |
0.2 - 1.5 mm² (24 - 16 AWG), solid
0.25 - 1.5 mm², flexible with ferrule |
| LED indicator |
Status indication of SmartWire-DT network: Green and orange LED
|
| Power consumption |
3 W for DILM 7-9 (Pick-up power)
4.5 W for DILM 12-15 (Pick-up power) 4.5 W for DILM 12-15 (Sealing power) 12 W for DILM 17-38 (Pick-up power) 3 W for DILM 7-9 (Sealing power) 0.5 W for DILM 17-38 (Sealing power) |
| Number of HW-interfaces (wireless) |
0
|
| Number of interfaces (PROFINET) |
0
|
| Permitted voltage at input - max |
15 V
|
| Permitted voltage at input - min |
15 V
|
| Permitted voltage at output - max |
28.8 V
|
| Permitted voltage at output - min |
20.4 V
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
0.8 W
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 60 Hz - max |
0 VAC
|
| Supply voltage at AC, 60 Hz - min |
0 VAC
|
| Supply voltage at DC - max |
15 VDC
|
| Supply voltage at DC - min |
15 VDC
|
| Time delay at signal exchange - max |
84 ms
|
| Time delay at signal exchange - min |
10 ms
|
| Product category |
SmartWire-DT slave
|
| Sealing current |
125 mA, SmartWire-DT network for DILM 7-9
21 mA, SmartWire-DT network for DILM 17-38 188 mA, SmartWire-DT network for DILM 12-15 |