Eaton Moeller® series SOL20 Switch-disconnector, DC current, 20A, 2 strings MC4
| Product Name |
Eaton Moeller® series P-SOL Switch-disconnector
|
| Catalog Number |
120915
|
| Product Length/Depth |
234 mm
|
| Product Height |
130 mm
|
| Product Width |
100 mm
|
| Product Weight |
0.888 kg
|
| Certifications |
IEC/EN 60947-3
|
| Catalog Notes |
MC4 connector (Stäubli)
|
| Product Category |
Switchgear for photovoltaic systems
|
| Features |
Isolating characteristics
|
| Actuator color |
Black
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Voltage release optional
|
| Operating frequency |
120 Operations/h
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Rated permanent current at AC-21, 400 V |
0 A
|
| Rated permanent current at AC-23, 400 V |
0 A
|
| Rated uninterrupted current (Iu) |
20 A
|
| Switching power at 400 V |
20 kW
|
| Rated operational voltage (Ue) at AC - min |
1000 V
|
| Device construction |
Complete device in housing
|
| Rated short-time withstand current (Icw) |
0.36 kA
|
| Electrical connection type of main circuit |
Other
|
| Design |
Enclosed
|
| Mounting position |
As required
|
| Actuator type |
Toggle
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Rated conditional short-circuit current (Iq) |
0 kA
|
| Degree of protection (front side) |
IP65
|
| Number of poles |
Two-pole
|
| Connection type |
MC4, Outputs
MC4, Inputs |
| Degree of protection |
NEMA Other
|
| Suitable for |
Ground mounting
Floor mounting |
| Locking facility |
Lockable in the 0 (Off) position
|
| Protection class |
2
|
| Number of switches |
1
|
| Resistance |
8 mΩ (internal)
|
| Lifespan, mechanical |
100,000 Operations
|
| Lifespan, electrical |
1,500 Operations
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Rated operating voltage (Ue) - max |
1000 V
|
| Rated operating voltage (Ue) - min |
1000 V
|
| Rated operational voltage (Ue) at AC - max |
1000 V
|
| Rated short-circuit making capacity (Icm) |
0.32 kA (up to 440 V, 50/60 Hz)
|
| Rated operational current (Ie) at DC-21A |
20 A
|
| Rated operational power at AC-23A, 400 V, 50 Hz |
0 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
| Housing color |
Other
|
| Housing material |
Plastic
|