Eaton SPX Variable frequency drive, 400 V AC, 3-phase, 37 kW, IP54, Radio interference suppression filter, OLED display, FR7
| Product Name |
Eaton SPX variable frequency drive
|
| Catalog Number |
125337
|
| Product Length/Depth |
189 mm
|
| Product Height |
630 mm
|
| Product Width |
237 mm
|
| Product Weight |
35 kg
|
| Certifications |
UL 508C
CE CSA Class No.: 3211-06 CUL IEC/EN61800-3 IEC/EN61800-5 RCM Specification for general requirements: IEC/EN 61800-2 IEC/EN 61800-3 DNV UL File No.: E134360 RoHS, ISO 9001 Safety: EN 61800-5-1: 2003 Certified by UL for use in Canada CSA-C22.2 No. 14 UL UL Category Control No.: NMMS, NMMS2, NMMS7. NMMS8 UL report applies to both US and Canada |
| Product Category |
Variable frequency drives
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
OLED display
Internal DC link IGBT inverter DC link choke Radio interference suppression filter |
| Climatic proofing |
< 95 % relative humidity, no condensation, no corrosion, no dripping water
|
| Connection to SmartWire-DT |
No
|
| Operating mode |
U/f control
Optional: Vector control with feedback (CLV) Sensorless vector control (SLV) |
| Frame size |
FR7
|
| Altitude |
Max. 1000 m
Above 1000 m with 1 % performance reduction per 100 m Max. 3000 m |
| Application in domestic and commercial area permitted |
No
|
| Application in industrial area permitted |
No
|
| Ambient operating temperature - max |
50 °C
|
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature at 150% overload - max |
50 °C
|
| Ambient operating temperature at 150% overload - min |
-10 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Assigned motor current IM at 400 V, 50 Hz, 110% overload |
81 A
|
| Assigned motor current IM at 400 V, 50 Hz, 150% overload |
68 A
|
| Mounting position |
Vertical
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Heat dissipation details |
Operation (with 150 % overload)
|
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| Voltage rating - max |
480 VAC
|
| Communication interface |
BACnet/IP, optional
DeviceNet, optional PROFIBUS-DP LonWorks, optional Modbus-TCP, optional CANopen®, optional BACnet MS/TP, optional EtherCAT, optional Ethernet IP, optional Modbus-RTU, optional PROFINET, optional |
| Converter type |
Other
|
| Degree of protection |
IP54
NEMA Other |
| Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
65 A
|
| Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
77 A
|
| System configuration type |
AC supply systems with earthed center point
|
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Assigned motor power at 460/480 V, 60 Hz |
50 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 110% overload |
60 HP
|
| Equipment heat dissipation, current-dependent Pvid |
925 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Output voltage (U2) |
480 V AC, 3-phase
500 V AC, 3-phase 400 V AC, 3-phase |
| Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
| Number of inputs (digital) |
6 (parameterizable, max. 30 V DC)
|
| Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
|
| Number of outputs (digital) |
1 (parameterizable, 48 V DC/50 mA)
|
| Number of relay outputs |
2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated control voltage (Uc) |
24 V DC (external, max. 250 mA)
|
| Supply frequency |
50/60 Hz
|
| Mains voltage - max |
500 V
|
| Mains voltage - min |
380 V
|
| Number of outputs (analog) |
1
|
| Output frequency - max |
320 Hz
|
| Output frequency - min |
0 Hz
|
| Suitable for |
Branch circuits, (UL/CSA)
|
| Switching frequency |
3.6 kHz, 1 - 10 kHz adjustable, fPWM, Power section, Main circuit
|
| Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase 500 V AC, 3-phase |
| Rated frequency - max |
66 Hz
|
| Rated frequency - min |
45 Hz
|
| Rated operational current (Ie) at 110% overload |
87 A
|
| Rated operational current (Ie) at 150% overload |
72 A
|
| Rated operational current for specified heat dissipation (In) |
72 A
|
| Rated operational power at 380/400 V, 50 Hz |
37 kW
|
| Rated operational power at 380/400 V, 50 Hz, 110% overload |
45 kW
|