Eaton SPX Variable frequency drive, 400 V AC, 3-phase, 900 kW, IP00, OLED display, FR14
| Product Name |
Eaton SPX variable frequency drive
|
| Catalog Number |
125486
|
| Product Length/Depth |
553 mm
|
| Product Height |
1032 mm
|
| Product Width |
708 mm
|
| Product Weight |
872 kg
|
| Certifications |
CUL
CSA-C22.2 No. 14 IEC/EN61800-3 UL DNV UL 508C IEC/EN 61800-3 Specification for general requirements: IEC/EN 61800-2 CE CSA Class No.: 3211-06 UL File No.: E134360 UL report applies to both US and Canada Certified by UL for use in Canada IEC/EN61800-5 UL Category Control No.: NMMS, NMMS2, NMMS7. NMMS8 RoHS, ISO 9001 Safety: EN 61800-5-1: 2003 RCM |
| Product Category |
Variable frequency drives
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
IGBT inverter
Internal DC link PC connection OLED display Control unit |
| Climatic proofing |
< 95 % relative humidity, no condensation, no corrosion, no dripping water
|
| Connection to SmartWire-DT |
No
|
| Operating mode |
Sensorless vector control (SLV)
U/f control Optional: Vector control with feedback (CLV) |
| Frame size |
FR14
|
| Altitude |
Above 1000 m with 1 % performance reduction per 100 m
Max. 1000 m Max. 3000 m |
| Application in domestic and commercial area permitted |
Yes
|
| Application in industrial area permitted |
Yes
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-10 °C
|
| Ambient operating temperature at 150% overload - max |
40 °C
|
| Ambient operating temperature at 150% overload - min |
-10 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Mounting position |
Vertical
|
| Relative symmetric net frequency tolerance |
10 %
|
| Relative symmetric net voltage tolerance |
10 %
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
| Heat dissipation details |
Operation (with 150 % overload)
|
| Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| Voltage rating - max |
480 VAC
|
| Communication interface |
CANopen®, optional
Modbus-TCP, optional PROFIBUS-DP LonWorks, optional BACnet/IP, optional DeviceNet, optional BACnet MS/TP, optional EtherCAT, optional Ethernet IP, optional Modbus-RTU, optional PROFINET, optional |
| Converter type |
U converter
|
| Degree of protection |
IP00
NEMA Other |
| Protocol |
CAN
DeviceNet PROFIBUS TCP/IP Data-Highway LON Other bus systems |
| System configuration type |
AC supply systems with earthed center point
|
| Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase |
1200 HP
|
| Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload |
1600 HP
|
| Equipment heat dissipation, current-dependent Pvid |
22500 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Functions |
4-quadrant operation possible
|
| Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase 500 V AC, 3-phase |
| Number of inputs (analog) |
2
|
| Number of inputs (digital) |
6
|
| Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
|
| Number of outputs (digital) |
1
|
| Number of phases (input) |
3
|
| Number of relay outputs |
2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
|
| Number of phases (output) |
3
|
| Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
| Rated control voltage (Uc) |
24 V DC (external, max. 250 mA)
|
| Supply frequency |
50/60 Hz
|
| Mains voltage - max |
500 V
|
| Mains voltage - min |
380 V
|
| Nominal output current I2N |
1770 A
|
| Number of HW-interfaces (industrial ethernet) |
0
|
| Number of HW-interfaces (other) |
1
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
1
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of interfaces (PROFINET) |
0
|
| Number of outputs (analog) |
1
|
| Output at linear load at rated output voltage - max |
900 kW
|
| Output at quadratic load at rated output voltage - max |
1000 kW
|
| Output frequency - max |
320 Hz
|
| Output frequency - min |
0 Hz
|
| Output voltage - max |
500 V
|
| Suitable for |
Branch circuits, (UL/CSA)
|
| Switching frequency |
3.6 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
| Rated operational voltage |
500 V AC, 3-phase
480 V AC, 3-phase 400 V AC, 3-phase |
| Rated frequency - max |
66 Hz
|
| Rated frequency - min |
45 Hz
|
| Rated operational current (Ie) at 110% overload |
1770 A
|
| Rated operational current (Ie) at 150% overload |
1600 A
|
| Rated operational current for specified heat dissipation (In) |
1600 A
|
| Rated operational power at 380/400 V, 50 Hz, 3-phase |
900 kW
|
| Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload |
1000 kW
|