| Product Name |
Eaton Moeller series NZM operating element
|
| Catalog Number |
125957
|
| Product Length/Depth |
380 mm
|
| Product Height |
100 mm
|
| Product Width |
140 mm
|
| Product Weight |
0.683 kg
|
| Compliances |
IEC
UL/CSA RoHS conform |
| Certifications |
Specially designed for North America
UL (File No. E140305) CSA (File No. 22086) UL489 CSA-C22.2 No. 5-09 UL (Category Control Number DIHS) IEC60947 CE marking CSA certified CSA (Class No. 1437-01) NFPA79 UL508A UL listed |
| Used with |
PN1(-4)
N1(-4) NZM1(-4) |
| Features |
Lockable
With red door coupling rotary handle for use of switch as emergency switching off device |
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Color |
Red
|
| Fitted with: |
Door coupling rotary handle with rotary drive
Add-on rotary handle on switch with "Deliberate Action" operation as per NFPA79 and UL508A Part 2 External warning plate/marking plate in German/English Black and yellow lightning symbol NZM1/2-XV4 shaft extension for mounting depth of 400 mm Padlock |
| Frame |
NZM1
|
| Suitable for |
Power circuit breaker
Emergency stop Switch disconnector |
| Cover/door type |
Door interlock can be modified such that it can be defeated from the outside using a screwdriver
After the door interlock is activated, must not be opened while on ON or TRIP. Must only be opened on OFF Door interlock not defeated in the locked OFF position. Door interlock on OFF with max. 3 padlocks |
| Locking facility |
Can also be modified in I position
Lockable on the switch in the 0 position With door interlock Lockable on the 0 position on the handle using up to 3 padlocks |
| Type |
Main switch assembly kit
|
| Special features |
|
| Degree of protection / NEMA enclosure type |
IP66
4X. 12 |