照片为代表
Download
Eaton SPX Variable frequency drive, 600 V AC, 3-phase, 250 kW, IP00, OLED display, FR10
Product Name |
Eaton SPX variable frequency drive
|
Catalog Number |
129602
|
Product Length/Depth |
506 mm
|
Product Height |
1165 mm
|
Product Width |
500 mm
|
Product Weight |
275 kg
|
Certifications |
IEC/EN 61800-3
UL File No.: E134360 RCM CUL CSA-C22.2 No. 14 UL 508C CSA Class No.: 3211-06 DNV IEC/EN61800-5 Safety: EN 61800-5-1: 2003 Certified by UL for use in Canada RoHS, ISO 9001 Specification for general requirements: IEC/EN 61800-2 UL report applies to both US and Canada UL Category Control No.: NMMS, NMMS2, NMMS7. NMMS8 CE IEC/EN61800-3 UL |
Product Category |
Variable frequency drives
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
IGBT inverter
Internal DC link Control unit OLED display PC connection |
Climatic proofing |
< 95 % relative humidity, no condensation, no corrosion, no dripping water
|
Connection to SmartWire-DT |
No
|
Operating mode |
Optional: Vector control with feedback (CLV)
Sensorless vector control (SLV) U/f control |
Frame size |
FR10
|
Altitude |
Above 1000 m with 1 % performance reduction per 100 m
Max. 1000 m Max. 3000 m |
Application in domestic and commercial area permitted |
Yes
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Mounting position |
Vertical
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload)
|
Rated operational power at 690 V, 50 Hz, 3-phase |
250 kW
|
Rated operational power at 690 V, 50 Hz, 3-phase, 110% overload |
315 kW
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Voltage rating - max |
690 VAC
|
Communication interface |
CANopen®, optional
PROFIBUS-DP DeviceNet, optional LonWorks, optional BACnet/IP, optional Modbus-TCP, optional BACnet MS/TP, optional EtherCAT, optional Ethernet IP, optional Modbus-RTU, optional PROFINET, optional |
Converter type |
U converter
|
Degree of protection |
IP00
NEMA Other |
Protocol |
PROFIBUS
Other bus systems DeviceNet LON CAN TCP/IP Data-Highway |
Assigned motor current IM at 690 V, 50 Hz, 110% overload |
316 A
|
Assigned motor current IM at 690 V, 50 Hz, 150% overload |
253 A
|
Assigned motor current IM at 690 V, 60 Hz, 110% overload |
251 A
|
Assigned motor current IM at 690 V, 60 Hz, 150% overload |
211 A
|
System configuration type |
AC supply systems with earthed center point
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 690 V, 60 Hz, 3-phase |
250 HP
|
Assigned motor power at 690 V, 60 Hz, 3-phase, 110 % overload |
300 HP
|
Equipment heat dissipation, current-dependent Pvid |
6250 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
690 V AC, 3-phase
600 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
6
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
|
Number of outputs (digital) |
1
|
Number of phases (input) |
3
|
Number of relay outputs |
2 (parameterizable, N/O, 8 A (24 V DC) / 8 A (250 V AC) / 0,4 A (125 V DC))
|
Number of phases (output) |
3
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
690 V
|
Mains voltage - min |
525 V
|
Nominal output current I2N |
325 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
250 kW
|
Output at quadratic load at rated output voltage - max |
315 kW
|
Output frequency - max |
320 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
690 V
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
600 V AC, 3-phase
690 V AC, 3-phase |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
325 A
|
Rated operational current (Ie) at 150% overload |
261 A
|
Rated operational current for specified heat dissipation (In) |
261 A
|