| Product Name |
Eaton CR contactor
|
| Catalog Number |
135201
|
| Product Length/Depth |
65 mm
|
| Product Height |
80 mm
|
| Product Width |
36 mm
|
| Product Weight |
0.25 kg
|
| Compliances |
RoHS conform
|
| Type |
4NO
|
| Amperage Rating |
25 A
|
| Number of poles |
Four-pole
|
| Features |
Additional equipment possible
Hum-free |
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Degree of protection |
IP20
|
| Equipment heat dissipation, current-dependent |
2.6 W
|
| Ambient operating temperature - max |
70 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Control voltage 1 - max |
253 V
|
| Control voltage 1 - min |
195.5 V
|
| Heat dissipation per pole, current-dependent |
2.2 W
|
| Incandescent lamp load - max |
2200 W
|
| Load fluorescent lamp - max |
1200 VA
|
| Load fluorescent lamp (duo circuit) - max |
1440 VA
|
| Load fluorescent lamp (parallel compensated) - max |
400 VA
|
| Number of contacts (change-over contacts) |
0
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally open contacts) |
4
|
| Number of modular spacings |
2
|
| Rated operating voltage (Ue) - max |
400 V
|
| Rated operating voltage (Ue) - min |
400 V
|
| Rated operational current for specified heat dissipation (In) |
25 A
|
| Utility category |
1
|
| Voltage rating (excitation) - max |
253 V
|
| Voltage rating (excitation) - min |
195.5 V
|
| Built-in depth |
60 mm
|
| Voltage type |
AC/DC
|
| Utilization category (according to EN IEC 60947-4-1) |
AC-1
|