Eaton Moeller® series PKE65 Circuit-breaker, Basic device with standard knob, Electronic, 65 A, Without overload releases
| Product Name |
Eaton Moeller® series PKE Motor-protective circuit-breaker
|
| Catalog Number |
138258
|
| Product Length/Depth |
187 mm
|
| Product Height |
162 mm
|
| Product Width |
55 mm
|
| Product Weight |
1.231 kg
|
| Compliances |
CE Marked
|
| Certifications |
CSA Std. C22.2 No. 14-10
IEC 60947-4-1 UL 508 VDE UL File No.: E36332 CE IEC/EN 60947 UL CSA CSA-C22.2 No. 60947-4-1-14 VDE 0660 CSA File No.: 165628 UL 60947-4-1 IEC/EN 60947-4-1 UL Category Control No.: NLRV CSA Class No.: 3211-05 |
| Features |
Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Standard knob
|
| Operating frequency |
60 Operations/h
|
| Pollution degree |
3
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
| Actuator type |
Turn button
|
| Adjustment range undelayed short-circuit release - max |
0 A
|
| Adjustment range undelayed short-circuit release - min |
0 A
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient operating temperature (enclosed) - max |
40 °C
|
| Ambient operating temperature (enclosed) - min |
-25 °C
|
| Ambient storage temperature - max |
80 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Equipment heat dissipation, current-dependent Pvid |
12.9 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
4.3 W
|
| Rated impulse withstand voltage (Uimp) |
6000 V AC
|
| Altitude |
Max. 2000 m
|
| Device construction |
Built-in device fixed built-in technique
|
| Connection |
Screw terminals
|
| Electrical connection type of main circuit |
Screw connection
|
| Lifespan, mechanical |
30,000 Operations (Main conducting paths)
|
| Overvoltage category |
III
|
| Degree of protection |
IP20
Terminals: IP00 |
| Number of poles |
Three-pole
|
| Lifespan, electrical |
50,000 operations (at 400V, AC-3)
|
| Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
|
| Functions |
Line and cable protection
Motor protection Motor protection for heavy starting duty System protection |
| Terminal capacity (solid/stranded AWG) |
14 - 2
|
| Switching capacity |
65 A, AC-3 up to 690 V
|
| Overload release current setting - max |
65 A
|
| Overload release current setting - min |
0 A
|
| Rated frequency - max |
60 Hz
|
| Rated frequency - min |
50 Hz
|
| Rated operational voltage (Ue) - max |
690 V
|
| Rated operational voltage (Ue) - min |
690 V
|
| Rated operational current for specified heat dissipation (In) |
65 A
|
| Rated operational power at AC-3e, 220/230 V, 50 Hz |
0 kW
|
| Rated operational power at AC-3e, 380/400 V, 50 Hz |
0 kW
|
| Rated uninterrupted current (Iu) |
65 A
|
| Static heat dissipation, non-current-dependent Pvs |
0 W
|
| Stripping length (main cable) |
14 mm
|
| Product category |
Motor protective circuit breaker
|
| Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
| Rated short-circuit breaking capacity Icu at 400 V AC |
0 kA
|
| Rated short-circuit breaking capacity Ics at 400 V AC |
0 kA
|
| Rated short-circuit breaking capacity Icu at 440 V AC |
0 kA
|
| Rated short-circuit breaking capacity Ics at 440 V AC |
0 kA
|
| Rated short-circuit breaking capacity Icu at 500 V AC |
0 kA
|
| Rated short-circuit breaking capacity Ics at 500 V AC |
0 kA
|
| Rated short-circuit breaking capacity Icu at 690 V AC |
0 kA
|
| Rated short-circuit breaking capacity Ics at 690 V AC |
0 kA
|
| Suitable for |
Also motors with efficiency class IE3
|
| Short-circuit release |
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks |
| Terminal capacity (solid) |
1 x (0.75 - 16) mm²
2 x (0.75 - 16) mm² |
| Rated operational current (Ie) |
65 A
|
| Temperature compensation |
-5 - 40 °C to IEC/EN 60947, VDE 0660
-25 - 55 °C, Operating range |
| Tightening torque |
1 Nm, Screw terminals, Control circuit cables
3.3 Nm, Screw terminals, Main cable |
| Switch off technique |
Electronic
|
| Terminal capacity (flexible with ferrule) |
2 x (0.75 - 25) mm², ferrule to DIN 46228
1 x (0.75 - 35) mm², ferrule to DIN 46228 |