| Product Name |
Eaton Moeller series xPole (Style 5) - mMC4/6/M MCB
|
| Catalog Number |
138903
|
| Product Length/Depth |
85 mm
|
| Product Height |
73 mm
|
| Product Width |
35 mm
|
| Product Weight |
0.24 kg
|
| Compliances |
RoHS conform
|
| Used with |
Z-FW/LP 248296 (Remote control and automatic switching device)
mMC4 Miniature circuit breaker |
| Amperage Rating |
10 A
|
| Features |
Additional equipment possible
|
| Accessories required |
ZP-IHK 286052
|
| Fitted with: |
Z-IS/SPE-1TE 274418
|
| Frame |
45 mm
|
| Pollution degree |
2
|
| Lifespan, mechanical |
20000 operations
|
| Mounting Method |
Quick attachment with 3 latch positions for top-hat rail IEC/EN 60715
|
| Degree of protection |
IP20
|
| Equipment heat dissipation, current-dependent |
3.9 W
|
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Busbar material thickness |
0.8 mm - 2 mm
|
| Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
| Terminals (top and bottom) |
Open mouthed/lift terminals
|
| Tripping characteristic |
B
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Built-in depth |
70.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
16 mm²
|
| Connectable conductor cross section (multi-wired) - min |
2 mm²
|
| Connectable conductor cross section (solid-core) - max |
35 mm²
|
| Connectable conductor cross section (solid-core) - min |
1.5 mm²
|
| Current limiting class |
3
|
| Frequency rating - max |
60 Hz
|
| Frequency rating - min |
50 Hz
|
| Heat dissipation capacity |
0 W
|
| Heat dissipation per pole, current-dependent |
0 W
|
| Width in number of modular spacings |
2
|
| Voltage type |
AC
|
| Overvoltage category |
III
|
| Number of poles |
Two-pole
|
| Lifespan, electrical |
10000 operations
|
| Release characteristic |
B
|
| Type |
|
| Special features |
|
| Application |
|
| Number of poles (protected) |
2
|
| Number of poles (total) |
2
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational current for specified heat dissipation (In) |
10 A
|
| Rated operational voltage (Ue) - max |
230 V
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V |
4.5 kA
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V |
4.5 kA
|
| Rated switching capacity (IEC/EN 60898-1) |
4.5 kA
|
| Static heat dissipation, non-current-dependent |
0 W
|
| Suitable for |
Flush-mounted installation
|