| Product Name |
Eaton XN Power supply module
|
| Catalog Number |
140070
|
| Product Length/Depth |
55.4 mm
|
| Product Height |
74.1 mm
|
| Product Width |
12.6 mm
|
| Product Weight |
0.025 kg
|
| Certifications |
UL Recognized
UL report applies to both US and Canada CSA Class No.: 2252-01, 2252-81 UL 508 IEC/EN 6113-2 UL Category Control No.: NRAQ, NRAQ7 IEC/EN 61000-6-2 CE CSA-C22.2 No. 142 IEC/EN 61000-6-4 IEC/EN 61131-2 cULus UL File No.: E205091 Certified by UL for use in Canada |
| Used with |
XN-P3T-SBB
XN-P4S-SBBC XN-P3S-SBB XN-P4T-SBBC |
| Type |
XI/ON power supply module
|
| Suitable as |
Segment module
|
| Features |
Fieldbus connection over separate bus coupler possible
|
| Air discharge |
According to EN 61000-4-2
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Screw-/spring clamp connection
|
| Fitted with: |
Potential separation
|
| Burst impulse |
According to IEC/EN 61000-4-4
|
| Admissible range |
18 - 30 V DC, Supply module
|
| Explosion safety category for dust |
None
|
| Environmental conditions |
Harmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation)
Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation) |
| Explosion safety category for gas |
None
|
| Mounting method |
Rail mounting possible
|
| Voltage type |
DC
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
0 °C
|
| Ambient storage temperature - max |
85 °C
|
| Ambient storage temperature - min |
-25 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Number of HW-interfaces (industrial ethernet) |
0
|
| Number of HW-interfaces (other) |
1
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of HW-interfaces (wireless) |
0
|
| Number of interfaces (PROFINET) |
0
|
| Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
| Emitted interference |
230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3)
30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3) |
| Electromagnetic fields |
According to IEC EN 61100-4-2
|
| Radiated RFI |
IEC/EN 61100-4-6
|
| Current consumption |
28 mA, from module bus, Supply modules
|
| Drop and topple |
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
|
| Relative humidity |
5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)
|
| Degree of protection |
IP20
|
| Protocol |
Other bus systems
|
| Residual ripple |
< 5 % (according to EN 61131-2)
|
| Suitable for |
Base modules with C-connection: 4-wire
Base modules without C-Connection: 2-/3-wire |
| Functions |
Bus diagnosis possible
|
| Field voltage |
24 V DC (UL)
|
| Vibration resistance |
According to IEC/EN 60068-2-6
|
| Shock resistance |
Mechanical, According to IEC/EN 60068-2-27
Continuous according to IEC/EN 60068-2-29 |
| Supply current |
10 A, IEI, Maximum operating current, Supply modules
|
| Number of bytes |
4 diagnostic bytes
|
| System accessory |
Yes
|
| Rated insulation voltage (Ui) |
500 V
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Static heat dissipation, non-current-dependent Pvs |
1.3 W
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 60 Hz - max |
0 VAC
|
| Supply voltage at AC, 60 Hz - min |
0 VAC
|
| Supply voltage at DC - max |
30 VDC
|
| Supply voltage at DC - min |
18 VDC
|
| Product category |
XN Slice module
|
| Potential isolation |
Through optocoupler: yes
|
| Power loss |
Normally 1.3 W
|
| Voltage dips |
According to EN 61131-2 (Voltage fluctuations/voltage dips)
|