Eaton Moeller® series P-SOL Undervoltage release, delayed, 230V50/60Hz, 240V50/60Hz
| Product Name |
Eaton Moeller® series P-SOL Accessory Undervoltage Release
|
| Catalog Number |
157859
|
| Product Length/Depth |
68 mm
|
| Product Height |
90 mm
|
| Product Width |
24 mm
|
| Product Weight |
0.138 kg
|
| Compliances |
CE
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Screw connection
|
| Fitted with: |
Internal delay for bridging intermittent voltage dips and fluctuations
|
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Rated operational voltage (Ue) at AC - max |
240 V
|
| Rated operational voltage (Ue) at AC - min |
230 V
|
| Static heat dissipation, non-current-dependent Pvs |
0.8 W
|
| Product category |
Accessories
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Number of contacts (change-over contacts) |
0
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally open contacts) |
0
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
| Voltage type |
AC
|
| Functions |
Delayed
|
| Suitable for |
Off-load switch
|
| Power consumption, pick-up, 50 Hz |
3 VA, Pull-in power, Coil in a cold state and 1.0 x Us
|
| Power consumption, pick-up, 60 Hz |
3 VA, Pull-in power, Coil in a cold state and 1.0 x Us
|
| Power consumption, sealing, 50 Hz |
3 VA, Coil in a cold state and 1.0 x Us
|
| Application |
|
| Power consumption, sealing, 60 Hz |
3 VA, Coil in a cold state and 1.0 x Us
|
| Pick-up voltage |
0.85 - 1.1 V x Uc
|
| Terminal capacity (solid/flexible with ferrule) |
1 x (0,75 - 2,5) mm²
2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) |
1 x (18 - 14)