Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 4p 250A 1500VDC
Product Name |
Eaton Moeller series NZM switch-disconnector
|
Catalog Number |
167690
|
Product Length/Depth |
149 mm
|
Product Height |
184 mm
|
Product Width |
140 mm
|
Product Weight |
3.5 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Amperage Rating |
250 A
|
Voltage rating |
1500 V - 1500 V
|
Circuit breaker frame type |
N2
|
Features |
Version as emergency stop installation
Motor drive optional Version as main switch Version as maintenance-/service switch Remote operation with shunt releases / remote operator |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
2
|
Mounting Method |
Ground mounting
Intermediate mounting Fixed Distribution board installation Built-in device fixed built-in technique |
Equipment heat dissipation, current-dependent |
66 W
|
Utilization category |
DC-22 A
|
Rated short-time withstand current (Icw) |
3.6 kA
|
Degree of protection |
Other
|
Electrical connection type of main circuit |
Screw connection
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Current rating (Iu) at 40°C with terminal jumpers |
250 A
|
Current rating (Iu) at 65°C with terminal jumpers |
200 A
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Rated insulation voltage (Ui) |
1500 V
|
Rated operating power at AC-23, 400 V |
0 kW
|
Rated operating power at AC-3, 400 V |
0 kW
|
Switch positions |
I, +, 0
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Rated operational current |
250 A (DC 22-A)
|
Degree of protection (IP), front side |
IP20
|
Number of poles |
Four-pole
|
Terminal capacity (copper strip) |
Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched) Min. 2 segments of 9 mm x 0.8 mm at box terminal Max. 8 segments of 15.5 mm x 0.8 mm (2x) at box terminal Max. 10 segments of 16 mm x 0.8 mm at box terminal |
Handle color |
Black
|
Functions |
Photovoltaic applications
Interlockable Disconnectors/main switches Voltage release optional |
Type |
DC switch-disconnector
|
Special features |
|
Application |
|
Number of switches |
1
|
Rated conditional short-circuit current (Iq) |
0 kA
|
Rated operating voltage (Ue) at AC - max |
0 V
|
Rated operational current for specified heat dissipation (In) |
250 A
|
Rated permanent current at AC-21, 400 V |
0 A
|
Rated permanent current at AC-23, 400 V |
0 A
|
Rated short-time withstand current (t = 1 s) |
3.6 kA
|
Switching power at 400 V |
0 kW
|
Handle type |
Rocker lever
|
Number of operations per hour - max |
120
|
Standard terminals |
Screw terminal
|
Terminal capacity (copper busbar) |
M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection Max. 24 mm x 8 mm direct at switch rear-side connection |
Terminal capacity (copper solid conductor/cable) |
10 mm² - 16 mm² (1x) direct at switch rear-side connection
4 mm² - 16 mm² (1x) at box terminal 4 mm² - 16 mm² (2x) at box terminal 4 mm² - 16 mm² (2x) direct at switch rear-side connection 16 mm² (1x) at tunnel terminal |
Terminal capacity (aluminum solid conductor/cable) |
16 mm² (1x) at tunnel terminal
|
Terminal capacity (copper stranded conductor/cable) |
25 mm² - 70 mm² (2x) at box terminal
25 mm² - 70 mm² (2x) direct at switch rear-side connection 25 mm² - 185 mm² (1x) direct at switch rear-side connection 25 mm² - 185 mm² (1x) at tunnel terminal 25 mm² - 185 mm² (1x) at box terminal |
Terminal capacity (aluminum stranded conductor/cable) |
25 mm² - 185 mm² (1x) at tunnel terminal
|