Eaton Moeller® series NAS Mains and system-protection device combination in the housing, 80A, 4p NAS80-CI-1
Product Name |
Eaton Moeller® series NAS Mains and system-protection device combination
|
Catalog Number |
168107
|
Product Length/Depth |
225 mm
|
Product Height |
563 mm
|
Product Width |
250 mm
|
Product Weight |
8 kg
|
Certifications |
VDE-AR-N 4105
|
Number of poles |
Four-pole
|
Type |
Mains and system-protection device combination
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Accessory/spare part type |
Other
|
Degree of protection |
IP65
|
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-20 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
-20 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Heat dissipation capacity Pdiss |
0 W
|
Rated breaking capacity at 380/400 V |
500 A
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
Connection type |
Screw terminals
|
Duty factor |
100 %
|
Terminal capacity |
1 x (25 - 50) mm², stranded, PE terminals
1 x (25 - 50) mm², flexible, PE terminals 1 x (16 - 50) mm², stranded, Main cables 1 x (2.5 - 35) mm², flexible, Main cables 1 x (16 - 50) mm², solid, PE terminals 1 x (2.5 - 16) mm², solid, Main cables |
Short-circuit protection rating |
Max. 160 A gG/gL 500 V, Fuse, 400V
|
Short-circuit current |
100 kA (prospective)
|
Power consumption |
90 VA at AC, 50/60 Hz (power consumption of the coil in a cold state and 1.0 x Us, Pick-up power, 2 x DILMP)
3 VA at AC, 50/60 Hz (power consumption of the coil in a cold state and 1.0 x Us, Sealing power, 2 x DILMP) |
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3) |
700 A
|
Rated operational power at 380/400 V, 50 Hz |
55 kW
|
Rated operational voltage (Ue) at AC - max |
400 V
|
Protection |
|
Product category |
|
Switching time |
< 150 ms with NA protection relay, Total opening delay
45 ms, Opening delay, Changeover time at 100 % US (recommended value) |