| Product Name |
Eaton EU5C Communication module
|
| Catalog Number |
171797
|
| Product Length/Depth |
127 mm
|
| Product Height |
90 mm
|
| Product Width |
35 mm
|
| Product Weight |
0.16 kg
|
| Certifications |
UL Category Control No.: NRQA
IEC/EN 61131-2 UL report applies to both US and Canada UL CSA UL File No.: E221530 |
| Features |
Potential isolation (Fieldbus Interface)
Overload proof |
| Air discharge |
8 kV, according to IEC 61131-2, level 3, ESD
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Pollution degree |
2
|
| Connection |
Used to connect the SmartWire-DT communication system to industrial field bus systems. Powers SmartWire-DT modules and switchgear
SmartWire-DT gateway for connecting up to 99 SmartWire-DT modules to an Industrial Ethernet network and for powering the SmartWire-DT modules and switchgear. SmartWire-DT blade terminal SWD4-8MF2 A connection to Powerlink can be established using the integrated 100 Mbit/s Ethernet hub as slave. |
| Burst impulse |
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
1 kV 2 kV, Supply cable, according to IEC/EN 61131-2, Level 3 |
| Climatic proofing |
In accordance with IEC 60068-2
|
| Operating mode |
Address allocation via Powerlink
|
| Air pressure |
795 - 1080 hPa (operation)
|
| Explosion safety category for dust |
None
|
| Explosion safety category for gas |
None
|
| Mounting method |
Wall mounting/direct mounting
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Screw fixing using fixing brackets ZB4-101-GF1 (accessories) Rail mounting possible |
| Voltage type |
DC
|
| Mounting position |
As required
|
| Contact discharge |
4 kV, according to IEC/EN 61131-2, Level 2, ESD
|
| Overvoltage category |
II
|
| Constant acceleration |
1 g, 9 - 150 Hz, according to IEC/EN 61131-2, Vibrations
|
| Constant amplitude |
3,5 mm, 5 - 9 Hz, according to IEC/EN 61131-2, Vibrations
|
| Surge rating |
0.5 kV, Supply cable, Surge (IEC/EN 61131-2:2008, Level 1), EMC
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
55 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Equipment heat dissipation, current-dependent Pvid |
4.4 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
0 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
| Electromagnetic fields |
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) |
| Product category |
SmartWire-DT coordinators
|
| Number of HW-interfaces CAN |
0
|
| Protection against polarity reversal |
Yes, for supply voltage (Siemens MPI optional)
Yes |
| Connection type |
2 x RJ45 (two-channel hub), Field bus interface
SWD: Plug, 8-pole Push in terminals, Supply voltage |
| Radiated RFI |
10 V (IEC/EN 61131-2:2008, Level 3)
|
| Number of modules |
99 (SmartWire-DT)
|
| Drop and topple |
50 mm Drop height, Drop to IEC/EN 60068-2-31
|
| Radio interference class |
Class A (EN 55011)
|
| Data transfer rate |
250 kBit/s, SmartWire-DT
100 MBit/s, Fieldbus interface 800 Byte, Fieldbus interface, Input data, max. 125 kBit/s, SmartWire-DT 542 Byte, Fieldbus interface, Output data, max. |
| Relative humidity |
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
|
| Degree of protection |
IP20
|
| Protocol |
Other bus systems
Powerlink V2 |
| Residual ripple |
≤ 5 % (input voltage)
|
| Rated control supply voltage |
24 V DC (UAUX, -15 %/+20 %)
24 V DC (UPOW, -15 %/+20 %) |
| Rated operational current (Ie) |
0.7 A
|
| Inrush current |
44 A (for 2 ms)
|
| Suitable for |
Safety functions
|
| Functions |
For connection to a POWERLINK field bus as a slave
|
| Station |
IP, Station address, Fieldbus interface
SmartWire-DT master, SmartWire-DT network |
| Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
| LED indicator |
Status indication of Supply voltage: LED
Status indication of SmartWire-DT master: Green and red LEDs Status indication of SmartWire-DT network: Configurable green or red LED |
| Interfaces |
Module type: Powerlink slave
Status display fieldbus interface for APL, SF, BF, LINK, RX/TX with Multi colour LED |
| System accessory |
Yes
|
| Potential isolation |
Between UPow and 15 V SmartWire-DT supply voltage: no
Supply voltage UAUX: no |
| Power loss |
Normally 1 W
|
| Voltage dips |
≤ 10 ms, Bridging voltage dips
|
| Number of HW-interfaces (industrial ethernet) |
2
|
| Number of HW-interfaces (other) |
0
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
1
|
| Number of HW-interfaces (wireless) |
0
|
| Number of interfaces (PROFINET) |
0
|
| Operating temperature - max |
55 °C
|
| Operating temperature - min |
-25 °C
|
| Rated operational voltage |
14.5 V (± 3 % - SmartWire-DT)
Typically UAUX -0.2 V (for 24 V DC slaves) |
| Short-circuit protection |
Yes, Short-circuit rating, SmartWire-DT supply voltage
No, external fuse FAZ Z3, Supply voltage UAux |
| Terminal capacity |
0.25 - 1.5 mm², flexible with ferrule
24 - 16 AWG, solid or stranded 0.2 - 1.5 mm², solid |
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Repetition rate |
1 s
|
| Static heat dissipation, non-current-dependent Pvs |
1 W
|
| Supply current - max |
0.7 mA
|
| Supply voltage at DC - max |
28.8 V
|
| Supply voltage at DC - min |
20.4 V
|