| Product Name |
Eaton XN-322 Input module
|
| Catalog Number |
178792
|
| Product Length/Depth |
104.2 mm
|
| Product Height |
16.8 mm
|
| Product Width |
80.3 mm
|
| Product Weight |
0.061 kg
|
| Certifications |
UL File No.: E135462
cULus CE EN 61131-2 EN 61000-6-2 EN 61000-6-4 UL508 CSA-C22.2 No. 142-M |
| Used with |
XN-312-…
XN300 |
| Type |
|
| Features |
Fieldbus connection over separate bus coupler possible
Input, thermocouple Analog outputs configurable Input, resistance thermometer Analog inputs configurable Input signal, configurable |
| Air discharge |
8 kV
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Plug-in connection
|
| Fitted with: |
Parameterizable Software input filter
2 kHz, third-order low-pass input filter |
| Pollution degree |
3
|
| Accuracy |
± 0.7 % of full scale, Temperature and resistance measurement
|
| Burst impulse |
2 kV, Supply cable
1 kV, Signal cable |
| Number of channels |
10, Analog Inputs
|
| Resolution |
16 Bit (Analog inputs)
|
| Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
| Air pressure |
795 - 1080 hPa (operation)
|
| Explosion safety category for dust |
None
|
| Rated operational current for specified heat dissipation (In) |
0 A
|
| Resolution of the analog inputs |
16 Bit
|
| Resolution of the analog outputs |
0 Bit
|
| Static heat dissipation, non-current-dependent Pvs |
3.04 W
|
| Stripping length (main cable) |
10 mm
|
| Supply voltage at AC, 50 Hz - max |
0 VAC
|
| Supply voltage at AC, 50 Hz - min |
0 VAC
|
| Supply voltage at AC, 60 Hz - max |
0 VAC
|
| Supply voltage at AC, 60 Hz - min |
0 VAC
|
| Supply voltage at DC - max |
30 VDC
|
| Supply voltage at DC - min |
18 VDC
|
| Product category |
XN-322 analog input module
|
| Power consumption |
2.6 W
|
| Environmental conditions |
Condensation: prevent with appropriate measures
|
| Input |
8 Analog thermocouple inputs
2 KTY inputs |
| Explosion safety category for gas |
None
|
| Mounting method |
Rail mounting possible
|
| Current consumption |
62 mA (typ.), for +5 V power supply (internal), Power supply - Input
75 mA (typ.), for +24 V, Power supply - Input |
| Voltage type |
DC
|
| Mounting position |
Horizontal
|
| Contact discharge |
4 kV
|
| Overvoltage category |
III
|
| Surge rating |
1 kV, Signal cable, unbalanced, EMC
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC |
| Emitted interference |
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency) |
| Potential isolation |
Analog inputs: no
|
| Electromagnetic fields |
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
| Load current |
Not specified by plug manufacturer
|
| Number of inputs (analog) |
10
|
| Radiated RFI |
10 V
|
| Protocol |
Other bus systems
|
| Relative humidity |
0 - 95 % (non-condensing)
|
| Connection type |
2 conductors, Temperature and resistance measurement
Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction |
| Rated operational voltage |
160 V (terminations)
|
| Degree of protection |
IP20
NEMA 1 |
| Gauge pin |
A1 (according to IEC/EN 60947-1)
|
| Vibration resistance |
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
|
| Shock resistance |
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
|
| Insulating material group |
I
|
| System accessory |
Yes
|
| Terminal capacity |
0.2 - 1.5 mm², flexible without ferrule, H07V-K
24 - 16 AWG 0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) 0.2 - 1.5 mm², solid, H07V-U 0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
| Value refresh time/cycle time |
Min. 1 / 1 ms (per channel / all channels), Analog Inputs
|
| Value representation |
SIGNED16 (0.1 °C), Temperature and resistance measurement
|
| Voltage dips |
Voltage dips: 10 ms/Voltage fluctuations: Yes
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
0 °C
|
| Ambient storage temperature - max |
85 °C
|
| Ambient storage temperature - min |
-20 °C
|
| Equipment heat dissipation, current-dependent Pvid |
0 W
|
| Heat dissipation capacity Pdiss |
0 W
|
| Heat dissipation per pole, current-dependent Pvid |
2.11 W
|
| Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
| Number of HW-interfaces (industrial ethernet) |
0
|
| Number of HW-interfaces (other) |
1
|
| Number of HW-interfaces (parallel) |
0
|
| Number of HW-interfaces (RS-232) |
0
|
| Number of HW-interfaces (RS-422) |
0
|
| Number of HW-interfaces (RS-485) |
0
|
| Number of HW-interfaces (serial TTY) |
0
|
| Number of HW-interfaces (USB) |
0
|
| Number of HW-interfaces (wireless) |
0
|
| Number of interfaces (PROFINET) |
0
|
| Number of outputs (analog) |
0
|
| Measured variables |
Temperature
|
| Measurement ranges |
0 - 1760 °C (Temperature measurement, Type S)
-20 - 80 °C (Temperature measurement, KTY10) 0 - 1080 °C (Temperature measurement, Type N) 0 - 690 °C (Temperature measurement, Type J) 0 - 520 °C (Temperature measurement, Type E) 0 - 680 °C (Temperature measurement, Type L) 0 - 590 °C (Temperature measurement, Type U) 0 - 400 °C (Temperature measurement, Type T) 0 - 1760 °C (Temperature measurement, Type R) 0 - 940 °C (Temperature measurement, Type K) 0 - 1820 °C (Temperature measurement, Type B) |