Eaton Moeller® series PKZM0 Motor-protective circuit-breaker, 3 pole, Ir = 25 - 32 A; Large packaging
| Product Name |
Eaton Moeller® series PKZM0 Motor-protective circuit-breaker
|
| Catalog Number |
180802
|
| Product Length/Depth |
76 mm
|
| Product Height |
93 mm
|
| Product Width |
45 mm
|
| Product Weight |
0.288 kg
|
| Actuator type |
Turn button
|
| Adjustment range undelayed short-circuit release - max |
496 A
|
| Adjustment range undelayed short-circuit release - min |
496 A
|
| Device construction |
Built-in device fixed built-in technique
|
| Connection |
Screw terminals
|
| Electrical connection type of main circuit |
Screw connection
|
| Degree of protection |
IP20
|
| Number of poles |
Three-pole
|
| Functions |
Phase failure sensitive
|
| Overload release current setting - max |
32 A
|
| Overload release current setting - min |
25 A
|
| Rated operational voltage (Ue) - max |
690 V
|
| Rated operational voltage (Ue) - min |
690 V
|
| Rated operational power at AC-3e, 220/230 V, 50 Hz |
7.5 kW
|
| Rated operational power at AC-3e, 380/400 V, 50 Hz |
15 kW
|
| Rated uninterrupted current (Iu) |
32 A
|
| Rated short-circuit breaking capacity Icu at 400 V AC |
40 kA
|
| Rated short-circuit breaking capacity Ics at 400 V AC |
10 kA
|
| Rated short-circuit breaking capacity Icu at 440 V AC |
10 kA
|
| Rated short-circuit breaking capacity Ics at 440 V AC |
3 kA
|
| Rated short-circuit breaking capacity Icu at 500 V AC |
3 kA
|
| Rated short-circuit breaking capacity Ics at 500 V AC |
3 kA
|
| Rated short-circuit breaking capacity Icu at 690 V AC |
3 kA
|
| Rated short-circuit breaking capacity Ics at 690 V AC |
1 kA
|
| Short-circuit current rating (group protection) |
10 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 150 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
10 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 125 A, 600 V High Fault, CB, SCCR (UL/CSA) 18 kA, 600 V High Fault, CB with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB with CL, SCCR (UL/CSA) 18 kA, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse with CL, SCCR (UL/CSA) 18 kA, 480 V High Fault, CB, SCCR (UL/CSA) with 600 A, 480 V High Fault, CB, SCCR (UL/CSA) 18 kA, 480 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 480 V High Fault, Fuse, SCCR (UL/CSA) |
| Switch off technique |
Thermomagnetic
|
| Power loss |
9.56 W
|