Eaton Moeller® series EMR6 Phase monitoring relays, Multi-functional, 300 - 500 V AC, 50/60 Hz
Product Name |
Eaton Moeller® series EMR6 Phase monitoring relay
|
Catalog Number |
184764
|
Product Length/Depth |
103.7 mm
|
Product Height |
85.6 mm
|
Product Width |
22.5 mm
|
Product Weight |
0.16 kg
|
Certifications |
GL
UL IEC CSA CCC |
Type |
Phase monitoring relay
|
Features |
Imbalance threshold values adjustable 2 - 25 % of mean value of phase voltages
|
Air discharge |
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
|
Electric connection type |
Screw connection
|
Pollution degree |
3
|
Power consumption |
3 VA
|
Burst impulse |
According to IEC/EN 61000-4-4, level 3
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
|
Rated impulse withstand voltage (Uimp) |
4000 V AC
|
Adjustable delay-on energization time - min |
0.1 s
|
Adjustable off-delay time - min |
0.1 s
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
85 °C
|
Ambient storage temperature - min |
40 °C
|
Measuring cycle |
50 ms
|
Number of contacts (change-over contacts) |
2
|
Number of contacts (normally closed contacts) |
0
|
Number of contacts (normally open contacts) |
0
|
Permitted delay-on energization time - max |
30 s
|
Permitted off-delay time - max |
30 s
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
500 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
300 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
500 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
300 V
|
Rated operational current (Ie) |
4 A at AC-12, 230 V
3 A at AC-15, 230 V 2 A at DC-13, 24 V 4 A at DC-12, 24 V |
Lifespan, electrical |
100,000 Operation (at 230 V, AC-12, 4 A)
|
Screwdriver size |
5.5 x 0.8 mm, Terminal screw
|
Voltage type |
AC
|
Connection type |
Snap fixing, top-hat rail IEC/EN 60715
|
Mounting position |
As required
|
Shock resistance |
Class 2
|
Overvoltage category |
III
|
Short-circuit protection rating |
Max. 10 A Fast/gL, Fuse, Relay output contacts
|
Duty factor |
100 %, Power supply
|
Degree of protection |
Enclosure: IP50
Terminals: IP20 |
Supply voltage |
300 - 500 V AC, 50/60 Hz
|
Delay time |
0.2 s, Response delay time
On-delay/off-delay: none = 0 or adjustable between 0.1 - 30 s |
Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
Electromagnetic compatibility |
According to IEC/EN 60947-6-2
|
Temperature error |
0.06 %/°C, Measuring circuits
|
Monitoring voltage |
300 - 500 V AC, 50/60 Hz (per phase)
|
Functions |
Under voltage detection
Phase failure detection Over voltage detection Multi-functional |
Hysteresis |
0 - 5 %
|
Immunity to line-conducted interference |
Level 3 (according to IEC/EN 61000-4-6)
|
Tightening torque |
0.8 Nm, Screw terminals
Min. 0.6 Nm, Screw terminals |
Immunity to radiation |
Level 3 (according to IEC/EN 61000-4-3)
|
Suitable for |
Three-phase networks
|
Voltage tolerance |
0.85 x Uc
1.1 x Uc |
Timing cycle |
0.06 %/°C, Time error within temperature range
0.5 % Error within supply voltage (Measuring circuits) 0.5 %, Time error within supply voltage Adjustable from 0.1 – 30 s, Reset delay/Off-delay time |
LED indicator |
Status indication of Phase sequence fault: Red, flashing light (F1 and F2 alternating)
Status indication of energized output relay: Green flashing (R) Status indication of Phase sequence error: Red LEDs (F1 and F2 flashing) Status indication of Overvoltage: F1 red, solid light Status indication of Relay energized: Yellow, solid light Status indication of Phase failure: F1 red, solid light and F2 red, flashing light Status indication of Supply voltage: Green, solid light Status indication of Delay time running: Yellow, flashing light Status indication of Phase failure: Red LEDs (F1 on, F2 flashes) Status indication of Imbalance: Red, solid light (F1 and F2) Status indication of Supply voltage: Green LED (R on) Status indication of Undervoltage: F2 red, solid light Status indication of Overvoltage: Red LED (F1 on) Status indication of Undervoltage: Red LED (F2 on) |
Lifespan, mechanical |
30,000,000 Operations
|
Monitoring function |
Phase imbalance monitoring
Phase failure Undervoltage Phase sequence monitoring Phase sequence (can be deactivated) Overvoltage Imbalance |
Rated control supply voltage (Us) at DC - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated frequency - max |
60 Hz
|
Rated frequency - min |
50 Hz
|
Rated operational voltage (Ue) at AC - max |
250 V
|
Voltage measurement - max |
500 V
|
Voltage measurement - min |
300 V
|
Product category |
EMR Measuring and monitoring relays
|
Terminal capacity |
1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule |
Voltage type of supply voltage |
AC
|
Voltage type of operating voltage |
AC
|
Rated switch current |
4 A
|
Supply voltage at AC, 50 Hz - min |
300 V
|
Supply voltage at AC, 50 Hz - max |
500 V
|
Supply voltage at AC, 60 Hz - min |
300 V
|
Supply voltage at AC, 60 Hz - max |
500 V
|
Operating voltage at AC, 50 Hz - min |
300 V
|
Operating voltage at AC, 50 Hz - max |
500 V
|
Operating voltage at AC, 60 Hz - min |
300 V
|
Operating voltage at AC, 60 Hz - max |
500 V
|