Eaton Moeller® series EMR6 Temperature monitor, 0 - +100 °C, 24 - 240 V AC, 50/60 Hz, 24 - 240 V DC
Product Name |
Eaton Moeller® series EMR6 Temperature monitoring relay
|
Catalog Number |
184787
|
Product Length/Depth |
103.7 mm
|
Product Height |
85.6 mm
|
Product Width |
22.5 mm
|
Product Weight |
0.151 kg
|
Certifications |
UL 508
CCC CE CSA-C22.2 No. 14 EAC GL |
Type |
Temperature monitor
|
Air discharge |
According to IEC/EN 61000-4-2 level 3
|
Electric connection type |
Screw connection
|
Pollution degree |
3
|
Power consumption |
2.9 VA
|
Burst impulse |
According to IEC/EN 61000-4-4, level 3
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
|
Rated impulse withstand voltage (Uimp) |
4000 V AC
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
-40 °C
|
Ambient storage temperature - max |
85 °C
|
Ambient storage temperature - min |
-40 °C
|
Number of contacts (change-over contacts) |
2
|
Number of contacts (normally closed contacts) |
0
|
Number of contacts (normally open contacts) |
0
|
Number of measuring circuits |
1
|
Product category |
EMR Measuring and monitoring relays
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
240 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
24 V
|
Rated control supply voltage (Us) at DC - max |
240 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Lifespan, electrical |
100,000 Operation (at 230 V, AC-12, 4 A)
|
Degree of protection |
Terminals: IP20
Enclosure: IP50 |
Screwdriver size |
4 x 0.8 mm, Terminal screw
|
Voltage type |
AC/DC
|
Connection type |
Snap fixing, top-hat rail IEC/EN 60715
|
Mounting position |
As required
|
Shock resistance |
Class 2
|
Contact discharge |
According to IEC/EN 61000-4-2, Level 3
|
Overvoltage category |
III
|
Duty factor |
100 %, Power supply
|
Supply voltage |
24 - 240 V DC
24 - 240 V AC, 50/60 Hz |
Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
Electromagnetic compatibility |
According to IEC/EN 60947-6-2
|
Hysteresis |
2 - 20 %
|
Immunity to line-conducted interference |
Level 3 (according to IEC/EN 61000-4-6)
|
Tightening torque |
Min. 0.5 Nm, Screw terminals
Max. 0.8 Nm, Screw terminals |
Immunity to radiation |
Level 3 (according to IEC/EN 61000-4-3)
|
Voltage tolerance |
0.85 x Uc
1.1 x Uc |
LED indicator |
Other states depending on fault (see IL): Measured value
Status indication of Supply voltage: Green, solid light |
Lifespan, mechanical |
30,000,000 Operations
|
Monitoring function |
Superheating and supercooling (window)
Supercooling Overheating |
Rated frequency - max |
60 Hz
|
Rated frequency - min |
50 Hz
|
Resistance measuring range - max |
0 Ω
|
Resistance measuring range - min |
0 Ω
|
Temperature measuring range - max |
100 °C
|
Temperature measuring range - min |
0 °C
|
Terminal capacity |
2 x (0.5-1.5) mm², (2 x (18-16) AWG), flexible with ferrule
1 x (0.5-2.5) mm², (1 x (18-14) AWG), solid |
Rated switch current |
4 A
|
Supply voltage at AC, 50 Hz - min |
24 V
|
Supply voltage at AC, 50 Hz - max |
240 V
|
Supply voltage at AC, 60 Hz - min |
24 V
|
Supply voltage at AC, 60 Hz - max |
240 V
|
Supply voltage at DC - min |
24 V
|
Supply voltage at DC - max |
240 V
|
Operating voltage at AC, 50 Hz - min |
24 V
|
Operating voltage at AC, 50 Hz - max |
240 V
|
Operating voltage at AC, 60 Hz - min |
24 V
|
Operating voltage at AC, 60 Hz - max |
240 V
|
Operating voltage at DC - min |
24 V
|
Operating voltage at DC - max |
240 V
|
Voltage type of supply voltage |
AC/DC
|
Voltage type of operating voltage |
AC/DC
|
Connection type (auxiliary circuit) |
Screw connection
|