| Product Name |
Eaton Moeller® series EMR6 Phase sequence relay
|
| Catalog Number |
184789
|
| Product Length/Depth |
103.7 mm
|
| Product Height |
85.6 mm
|
| Product Width |
22.5 mm
|
| Product Weight |
0.16 kg
|
| Certifications |
IEC/EN 60255-6
|
| Type |
Phase sequence relay
|
| Features |
Fixed response delay
|
| Air discharge |
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
|
| Electric connection type |
Screw connection
|
| Pollution degree |
3
|
| Power consumption |
11 VA
|
| Burst impulse |
According to IEC/EN 61000-4-4, level 3
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
|
| Rated impulse withstand voltage (Uimp) |
4000 V AC
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-20 °C
|
| Ambient storage temperature - max |
85 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Measuring cycle |
500 ms
|
| Number of contacts (change-over contacts) |
2
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (normally open contacts) |
0
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
500 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
200 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
500 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
200 V
|
| Rated operational current (Ie) |
2 A at DC-13, 24 V
4 A at AC-12, 230 V 4 A at DC-12, 24 V 3 A at AC-15, 230 V |
| Lifespan, electrical |
300,000 Operation (at 230 V, AC-12, 4 A)
|
| Screwdriver size |
5.5 x 0.8 mm, Terminal screw
|
| Voltage type |
AC
|
| Connection type |
Snap fixing, top-hat rail IEC/EN 60715
|
| Mounting position |
As required
|
| Shock resistance |
Class 2
|
| Overvoltage category |
III
|
| Short-circuit protection rating |
Max. 10 A Fast/gL, Fuse, Relay output contacts
|
| Duty factor |
100 %, Power supply
|
| Degree of protection |
Enclosure: IP50
Terminals: IP20 |
| Supply voltage |
200 - 500 V AC, 50/60 Hz
|
| Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
| Electromagnetic compatibility |
According to IEC/EN 60947-6-2
|
| Temperature error |
0.06 %/°C, Measuring circuits
|
| Monitoring voltage |
200 - 500 V AC, 50/60 Hz (per phase)
200 - 500 V AC |
| Functions |
Phase failure detection
Monitoring of three-phase networks |
| Immunity to line-conducted interference |
Level 3 (according to IEC/EN 61000-4-6)
|
| Tightening torque |
Min. 0.5 Nm, Screw terminals
0.8 Nm, Screw terminals |
| Immunity to radiation |
Level 3 (according to IEC/EN 61000-4-3)
|
| Voltage tolerance |
0.85 x Uc
1.1 x Uc |
| Timing cycle |
0.5 % Error within supply voltage (Measuring circuits)
|
| LED indicator |
Status indication of energized output relay: Yellow LED
Status indication of Phase failure: Red, solid light Status indication of Phase sequence fault: Red, flashing light |
| Lifespan, mechanical |
30,000,000 Operations
|
| Monitoring function |
Phase failure
Phase sequence monitoring Phase sequence |
| Rated control supply voltage (Us) at DC - max |
0 V
|
| Rated control supply voltage (Us) at DC - min |
0 V
|
| Rated frequency - max |
60 Hz
|
| Rated frequency - min |
50 Hz
|
| Rated operational voltage (Ue) at AC - max |
250 V
|
| Voltage measurement - max |
500 V
|
| Voltage measurement - min |
200 V
|
| Product category |
EMR Measuring and monitoring relays
|
| Terminal capacity |
2 x 2.5 mm², solid
2 x 2.5 mm², (2 x 14 AWG), flexible with ferrule |
| Voltage type of supply voltage |
AC
|
| Voltage type of operating voltage |
AC
|
| Rated switch current |
4 A
|
| Supply voltage at AC, 50 Hz - min |
200 V
|
| Supply voltage at AC, 50 Hz - max |
500 V
|
| Supply voltage at AC, 60 Hz - min |
200 V
|
| Supply voltage at AC, 60 Hz - max |
500 V
|
| Operating voltage at AC, 50 Hz - min |
200 V
|
| Operating voltage at AC, 50 Hz - max |
500 V
|
| Operating voltage at AC, 60 Hz - min |
200 V
|
| Operating voltage at AC, 60 Hz - max |
500 V
|