Eaton Moeller® series EMS2 DOL starter, 24 V DC, 1,5 - 7 (AC-53a), 9 (AC-51) A, Push in terminals, SmartWire-DT slave, Controlled stop, PTB 19 ATEX 3000
Product Name |
Eaton Moeller® series EMS2 DOL starter
|
Catalog Number |
192389
|
Product Length/Depth |
114.5 mm
|
Product Height |
99 mm
|
Product Width |
22.5 mm
|
Product Weight |
0.297 kg
|
Certifications |
UL508
IEC 61508 EN ISO 13849 IEC/EN 60947-4-2 UL File No.: E338590 UL Category Control No.: NLDX, NLDX7 PTB 19 ATEX 3000 UL 60947-4-1 CSA-C22.2 No. 60947-4-1-14 CE marking UL listed Certified by UL for use in Canada UL report applies to both US and Canada |
Type |
DOL starter (complete device)
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Class |
CLASS 10
|
Connection to SmartWire-DT |
Yes
|
Model |
Direct starter
|
Explosion safety category for dust |
ATEX dust-ex-protection, II (2) G [Ex e] [Ex d] [Ex px]
ATEX dust-ex-protection, II (2) D [Ex t] [Ex p] |
Electrical connection type of main circuit |
Spring clamp connection
|
Voltage type |
DC
|
Mounting position |
Motor feeder at bottom
Vertical |
Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Rail mounting possible |
Connection |
Push in terminals
|
Functions |
Controlled stop
Temperature compensated overload protection For connecting to SmartWire-DT for expanded diagnostics DOL starting Motor protection Automatic reset Display of Device Type Display of Enable signal Manual reset Display of Motor current in % Display of Operating direction feedback Operating the motor starter Display of Operational readiness Display of Overload prewarning Display of Set short-circuit release value Display of Thermal motor image in % Display of Trip indications (overload, phase failure, etc.) |
Terminal capacity |
0.2 - 2.5 mm², Main cables, Push-in terminals
|
Terminal capacity (AWG) |
24 - 14, Push-in terminals
|
Overload release current setting - min |
1.5 A
|
Power consumption (sealing) at DC |
12 W
|
Rated actuating current (Ic) |
5 mA
|
Rated conditional short-circuit current (Iq), type 2, 230 V |
0 A
|
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V |
0 A
|
Rated conditional short-circuit current, type 1, 480 Y/277 V |
0 A
|
Rated conditional short-circuit current, type 1, 600 Y/347 V |
0 A
|
Rated control supply current Is |
60 mA
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
7 A
|
Radio interference class |
EN 55011
Class A (EN 61000-6-3, emitted interference, radiated) |
Residual ripple |
≤ 5 % (input voltage)
|
Rated control supply voltage |
19.2 - 30 V DC
|
Protocol |
Other bus systems
|
Inrush current |
120 mA (draw)
|
Rated control voltage (Uc) |
24 V (Actuating circuit ON, L, R)
|
Rated operational current (Ie) |
9 A
|
Rated operational current (Ie) at AC-51 |
9 A
|
Rated operational current (Ie) at AC-53A - max |
7 A
|
Rated operational current for specified heat dissipation (In) |
9 A
|
Rated operational voltage |
42 - 550 V
500 V AC |
Safety parameter (EN ISO 13849-1) |
3, Category
PL e, Performance level 60 (safe switch off) / 82 (motor protection) years; MTTFD |
Safety parameter (IEC 62061) |
Opening delay [ms]: 200 (safe switch off) / Class 10A (motor protection)
99 % (safe switch off) / 98 % (motor protection), DC |
Switching level |
19.2 - 30 V DC, Switching level "High", Actuating circuit (ON, L, R)
< 5 V DC, Switching level "confirm Off", Actuating circuit (ON, L, R) -3 - 9.6 V DC, Switching level "Low", Actuating circuit (ON, L, R) |
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-5 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
40 °C
|
Equipment heat dissipation, current-dependent Pvid |
12 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of command positions |
0
|
Number of pilot lights |
0
|
Overload release current setting - max |
9 A
|
Rated operational power at AC-3, 220/230 V, 50 Hz |
1.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
3 kW
|
Rated operational power at AC-53A, 380/400 V, 50 Hz |
3 kW
|
Rated power at 460 V, 60 Hz, 3-phase |
0 kW
|
Rated power at 575 V, 60 Hz, 3-phase |
0 kW
|
Static heat dissipation, non-current-dependent Pvs |
2 W
|
Heat dissipation details |
If necessary, Allow for derating
|
Product category |
Electronic motor starter
|
Coordination class (IEC 60947-4-3) |
Class 1
|
Degree of protection |
IP20
NEMA Other |
Electrical connection type for auxiliary- and control-current circuit |
Spring clamp connection
|
Actuating voltage |
24 V DC
|
Power consumption |
12 W
|