照片为代表
Download
Eaton Moeller® series NAS Mains and system-protection device combination in the housing, 63A, 4p NAS63-CI-2
| Product Name |
Eaton Moeller® series NAS Mains and system-protection device combination
|
| Catalog Number |
198273
|
| Product Length/Depth |
225 mm
|
| Product Height |
563 mm
|
| Product Width |
250 mm
|
| Product Weight |
6.8 kg
|
| Certifications |
VDE-AR-N 4105
|
| Number of poles |
Four-pole
|
| Type |
Mains and system-protection device combination
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Accessory/spare part type |
Other
|
| Degree of protection |
IP65
|
| Ambient operating temperature - max |
40 °C
|
| Ambient operating temperature - min |
-20 °C
|
| Ambient operating temperature (enclosed) - max |
40 °C
|
| Ambient operating temperature (enclosed) - min |
-20 °C
|
| Ambient storage temperature - max |
80 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Rated breaking capacity at 380/400 V |
400 A
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
| Connection type |
Screw terminals
|
| Duty factor |
100 %
|
| Terminal capacity |
1 x (25 - 50) mm², stranded, PE terminals
1 x (2.5 - 35) mm², flexible, Main cables 1 x (25 - 50) mm², flexible, PE terminals 1 x (2.5 - 16) mm², solid, Main cables 1 x (16 - 50) mm², solid, PE terminals 1 x (16 - 50) mm², stranded, Main cables |
| Short-circuit protection rating |
Max. 125 A gG/gL 500 V, Fuse, 400V
|
| Short-circuit current |
100 kA (prospective)
|
| Power consumption |
1.5 VA at AC, 50/60 Hz (power consumption of the coil in a cold state and 1.0 x Us, Sealing power)
45 VA at AC, 50/60 Hz (power consumption of the coil in a cold state and 1.0 x Us, Pick-up power) |
| Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3) |
560 A
|
| Rated operational power at 380/400 V, 50 Hz |
43 kW
|
| Rated operational voltage (Ue) at AC - max |
400 V
|
| Protection |
|
| Product category |
Switchgear for renewable energies
|
| Switching time |
45 ms, Opening delay, Changeover time at 100 % US (recommended value)
< 150 ms with NA protection relay, Total opening delay |