Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 6.8 kW, 1 N/O, 1 NC, 230 V 50/60 Hz, AC operation, Push in terminals
Product Name |
Eaton Moeller® series DILM contactor
|
Catalog Number |
199664
|
Product Length/Depth |
115 mm
|
Product Height |
85 mm
|
Product Width |
45 mm
|
Product Weight |
0.441 kg
|
Certifications |
VDE 0660
IEC/EN 60947 |
Number of poles |
Three-pole
|
Fitted with: |
Mirror contact
|
Operating frequency |
5000 mechanical Operations/h (AC operated)
|
Pollution degree |
3
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Connection to SmartWire-DT |
No
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Utilization category |
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Connection |
Push in terminals
|
Frame size |
FS2
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Conventional thermal current Ith (1-pole, enclosed) |
80 A
|
Conventional thermal current Ith (3-pole, enclosed) |
32 A
|
Conventional thermal current Ith at 55°C (3-pole, open) |
37 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
88 A
|
Application |
Contactors for Motors
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Arcing time |
10 ms
|
Electrical connection type of main circuit |
Push-in connection
|
Screwdriver size |
3 x 0.5 mm, Terminal screw
3.0 x 0.5 mm, Terminal screw |
Voltage type |
AC
|
Degree of protection |
IP20
|
Number of auxiliary contacts (normally closed contacts) |
1
|
Number of auxiliary contacts (normally open contacts) |
1
|
Number of contacts (normally closed contacts) |
1
|
Number of contacts (normally closed) as main contact |
0
|
Number of contacts (normally open contacts) |
1
|
Number of main contacts (normally open contact) |
3
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
230 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
230 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
230 V
|
Drop-out voltage |
AC operated: 0.6 - 0.3 x UC, AC operated
|
Overvoltage category |
III
|
Duty factor |
100 %
|
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
Pick-up voltage |
0.8 - 1.1 V AC x Uc
|
Power consumption, pick-up, 50 Hz |
58 VA, Dual-frequency coil in a cold state and 1.0 x Us
62 VA, Dual-frequency coil in a cold state and 1.0 x Us |
Safe isolation |
400 V AC, Between the contacts, According to EN 61140
400 V AC, Between coil and contacts, According to EN 61140 |
Power consumption, pick-up, 60 Hz |
62 VA, Dual-frequency coil in a cold state and 1.0 x Us
58 VA, Dual-frequency coil in a cold state and 1.0 x Us |
Power consumption, sealing, 50 Hz |
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
|
Power consumption, sealing, 60 Hz |
9.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
6.5 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz 2.1 W, Dual-frequency coil in a cold state and 1.0 x Us |
Terminal capacity (flexible with unisolated ferrule) |
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (0.5 - 2.5) mm², Control circuit cables 1 x (1 - 6) mm², Main cables 2 x (1 - 6) mm², Main cables |
Terminal capacity (flexible with ultrasonic welded cable end) |
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (0.5 - 2.5) mm², Control circuit cables 1 x (1 - 10) mm², Main cables 2 x (1 - 6) mm², Main cables |
Rated operational current (Ie) |
14 A at AC-3, 220/230 V
|
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm² |
Shock resistance |
7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 6.5 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 8 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 2 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms |
Terminal capacity (solid) |
1 x (0.5 - 0.25) mm²
2 x (0.5 - 2.5) mm², Control circuit cables 1 x (1 - 6) mm² 2 x (1 - 6) mm² |
Terminal capacity (solid/stranded AWG) |
20 - 14
18 - 8, Main cables |
Terminal capacity (flexible) |
2 x (1-6) mm²
1 x (0.5 - 2.5) mm² 2 x (0.5 - 2.5) mm² 1 x (1 - 10) mm² |
Rated control supply voltage (Us) at DC - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated insulation voltage (Ui) |
690 V
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
40 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
14 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
14 A
|
Rated operational current (Ie) at AC-3, 440 V |
14 A
|
Rated operational current (Ie) at AC-3, 500 V |
10 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
7 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
7 A
|
Rated operational current (Ie) at AC-4, 400 V |
7 A
|
Rated operational current (Ie) at AC-4, 440 V |
7 A
|
Rated operational current (Ie) at AC-4, 500 V |
6 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
5 A
|
Rated operational power at AC-3, 240 V, 50 Hz |
3.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
5.5 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
7 kW
|
Rated operational power at AC-4, 220/230 V, 50 Hz |
2 kW
|
Rated operational power at AC-4, 240 V, 50 Hz |
2.2 kW
|
Rated operational power at AC-4, 380/400 V, 50 Hz |
3 kW
|
Rated operational power at AC-4, 415 V, 50 Hz |
3.4 kW
|
Rated operational power at AC-4, 440 V, 50 Hz |
3.6 kW
|
Rated operational power at AC-4, 500 V, 50 Hz |
3.5 kW
|
Rated operational power at AC-4, 660/690 V, 50 Hz |
4.4 kW
|
Rated operational power (NEMA) |
0 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Switching time (AC operated, make contacts, closing delay) - max |
22 ms
|
Switching time (AC operated, make contacts, closing delay) - min |
16 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
14 ms
|
Switching time (AC operated, make contacts, opening delay) - min |
8 ms
|
Short-circuit current rating (high fault at 480 V) |
65 kA, CB, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA) |
Suitable for |
Also motors with efficiency class IE3
|
Operating voltage at AC, 50 Hz - min |
24 V
|
Operating voltage at AC, 50 Hz - max |
690 V
|
Operating voltage at AC, 60 Hz - min |
24 V
|
Operating voltage at AC, 60 Hz - max |
690 V
|