Eaton Moeller® series P3 On-Off switch, P3, 63 A, surface mounting, 3 pole, STOP function, With black rotary handle and locking ring, Lockable in the 0 (Off) position
| Product Name |
Eaton Moeller® series P3 Main switch
|
| Catalog Number |
207336
|
| Product Length/Depth |
160 mm
|
| Product Height |
222 mm
|
| Product Width |
120 mm
|
| Product Weight |
0.948 kg
|
| Compliances |
CE
|
| Product Category |
On-Off switch
|
| Features |
Version as main switch
Version as maintenance-/service switch |
| Actuator color |
Black
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
Black rotary handle and locking ring
|
| Rated permanent current at AC-21, 400 V |
63 A
|
| Rated permanent current at AC-23, 400 V |
63 A
|
| Rated uninterrupted current (Iu) |
63 A
|
| Switching power at 400 V |
30 kW
|
| Accessories |
Auxiliary contact or neutral conductor fitted by user.
|
| Device construction |
Complete device in housing
|
| Rated short-time withstand current (Icw) |
1.26 kA
|
| Electrical connection type of main circuit |
Screw connection
|
| Actuator type |
Other
|
| Number of auxiliary contacts (change-over contacts) |
0
|
| Number of auxiliary contacts (normally closed contacts) |
0
|
| Rated conditional short-circuit current (Iq) |
4 kA (Load side)
100 kA (Supply side) |
| Degree of protection (front side) |
IP65
|
| Number of poles |
3
|
| Mounting method |
Surface mounting
|
| Degree of protection |
NEMA 12
|
| Suitable for |
Ground mounting
|
| Locking facility |
Lockable in the 0 (Off) position
|
| Functions |
STOP function
Interlockable |
| Number of switches |
1
|
| Number of auxiliary contacts (normally open contacts) |
0
|
| Rated operating voltage (Ue) - max |
690 V
|
| Rated operating voltage (Ue) - min |
690 V
|
| Rated operational voltage (Ue) at AC - max |
690 V
|
| Rated operational power at AC-23A, 400 V, 50 Hz |
37 kW
|
| Rated operational power at AC-3, 380/400 V, 50 Hz |
30 kW
|
| Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|