Eaton XIOC Communication module for XC100/200, 24 V DC, PROFIBUS-DP master
Product Name |
Eaton XIOC Communication module
|
Catalog Number |
257908
|
Product Length/Depth |
100 mm
|
Product Height |
95 mm
|
Product Width |
30 mm
|
Product Weight |
0.145 kg
|
Certifications |
CSA-C22.2 No. 0-M
CSA-C22.2 No. 142-M CE UL CSA Class No.: 2252-01 IEC/EN 61131-2 UL Category Control No.: NRAQ EN 50178 CSA CSA File No.: 012528 UL File No.: E135462 UL508 |
Used with |
XC100/200 (expandable with up to 15 XI/OC modules)
|
Type |
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Potential separation
|
Pollution degree |
2
|
Bus termination |
Switchable
|
Explosion safety category for dust |
None
|
Explosion safety category for gas |
None
|
Overvoltage category |
II
|
Supply voltage |
20.4 – 28.8 (11.8 – 14.4) V DC, Admissible range, Power supply
|
Emitted interference |
Class A (according to DIN/EN 55011/22)
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
0 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-20 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Number of slots |
3
|
Terminals |
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
|
Protection class |
1
|
Number of modules |
3 (XC200)
124 (slaves) 1 (XC100) |
Current consumption |
300 mA, Interfaces
300 mA (Ie), Interfaces |
Data transfer rate |
93.75 kBit/s with 1200 m
9.6 - 12000 kBit/s 500 kBit/s with 400 m 1500 kBit/s with 200 m Transmit data: 3500 Byte 9.6 kBit/s with 1200 m 3000 kBit/s with 100 m 19.2 kBit/s with 1200 m 12000 kBit/s with 100 m 187.5 kBit/s with 1000 m 6000 kBit/s with 100 m Receive data: 3500 Bytes |
Degree of protection |
IP20
|
Protocol |
PROFIBUS
|
Residual ripple |
≤ 5 %
|
Resistance |
500 g/⌀ 50 mm ±25 g (impact resistance)
|
Data transmission type |
Serial
|
Functions |
Master (Class 1)
PROFIBUS-DP interface |
Vibration resistance |
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm |
Shock resistance |
15 g, Mechanical, Shock duration 11 ms
|
Transmission rate |
12000 kBit/s
|
LED indicator |
Status indication of Bus diagnostics: LED
|
Interfaces |
PROFIBUS DP, RS485, EN 50170 (built-in)
Max. 244 Bytes per slave (Inputs/outputs) |
Potential isolation |
Interfaces: yes
|
Power loss |
7.2 W
|
Voltage dips |
10 ms
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Rated operational voltage |
24 (12) V DC
|
Plug type |
9-pole SUB-D socket
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Repetition rate |
1 s
|
Static heat dissipation, non-current-dependent Pvs |
7.2 W
|
Supply voltage at DC - max |
5 V
|