照片为代表
Download
| Product Name |
Eaton Moeller series NZM Undervoltage release
|
| Catalog Number |
266208
|
| Product Length/Depth |
107 mm
|
| Product Height |
51 mm
|
| Product Width |
64 mm
|
| Product Weight |
0.218 kg
|
| Compliances |
UL/CSA
IEC RoHS conform |
| Certifications |
UL (File No. E140305)
CSA (File No. 22086) CSA certified CSA (Class No. 1437-01) UL489 CE marking UL listed CSA-C22.2 No. 5-09 IEC60947 UL (Category Control Number DIHS) |
| Used with |
NZM4(-4), N(S)4(-4)
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Electric connection type |
Screw connection
|
| Frame |
NZM4
|
| Minimum command time - max |
15 ms
|
| Minimum command time - min |
10 ms
|
| Number of contacts (normally open contacts) |
0
|
| Reaction time |
23 ms
|
| Pick-up power consumption at AC (undervoltage release) |
3.6 VA
|
| Pick-up power consumption at DC (undervoltage release) |
2.5 W
|
| Voltage tolerance - max |
1.1
|
| Voltage tolerance - min |
0.85
|
| Rated control supply voltage |
220 - 250 V DC
|
| Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
| Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
| Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
| Suitable for |
Off-load switch
|
| Connection type |
With bolt connection
|
| Voltage type |
AC
|
| Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
| Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
| Terminal capacity (solid/flexible conductor) |
18 - 14 AWG (2x) at shunt release
18 - 14 AWG (2x) for undervoltage releases, off-delayed 18 - 14 AWG (1x) at shunt release 18 - 14 AWG (1x) for undervoltage releases, off-delayed 0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule 0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule 0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule 0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule |
| Type |
Accessory
Undervoltage release
|
| Special features |
Non-delayed disconnection of NZM circuit-breaker or N switch-disconnector when the control voltage sinks below 35 – 70% US.
For use with emergency-stop devices in connection with an emergency-stop button.
When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
|
| Power consumption |
3.6 VA (Sealing AC)
2.5 W (sealing DC) |
| Rated control supply voltage (Us) at DC - max |
250 V
|
| Rated control supply voltage (Us) at DC - min |
220 V
|
| Number of contacts (normally closed contacts) |
0
|
| Number of contacts (change-over contacts) |
0
|
| Undelayed short-circuit release - min |
0 A
|
| Undelayed short-circuit release - max |
0 A
|
| Rated control voltage (relay contacts) |
220 V DC
250 V DC |