Eaton Moeller series NZM - Molded Case Circuit Breaker. Fieldbus connection, profibus-DPV1-Slave
| Product Name |
Eaton Moeller series NZM electronic accessory
|
| Catalog Number |
270333
|
| Product Length/Depth |
60 mm
|
| Product Height |
90 mm
|
| Product Width |
36 mm
|
| Product Weight |
0.102 kg
|
| Compliances |
RoHS conform
|
| Certifications |
IEC 60068-2-27
IEC/EN 61000-4 EN 55011 EN 55022 IEC 60068-2-6 |
| Used with |
Diagnostics, communication
|
| Special features |
|
| Type |
Accessory
|
| Voltage rating |
24 V (-15/+20 %)
|
| Accessories required |
Separate external bus termination
|
| 10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Pollution degree |
2 (EMC)
|
| Burst impulse |
2 kV
|
| Isolation |
Between bus and power supply (simple), between bus and power supply and NZM-XDMI612 (safe potential isolation)
|
| Accessory/spare part type |
Diagnostics and communication
|
| Display |
Profibus-DP LED (BUS): red
|
| Explosion safety category for dust |
Other
|
| Explosion safety category for gas |
None
|
| Mounting method |
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Front build in possible Rail mounting possible |
| Voltage type |
DC
|
| Acyclic network services |
Display/match protection settings, event list, identification, hours of operation, switching operations, time
|
| Mounting position |
Vertical or horizontal
|
| Dimensions |
35.5 mm x 90 mm x 58 mm
|
| Interface type |
RS485
|
| Safety performance level (EN ISO 13849-1) |
None
|
| SIL (IEC 61508) |
None
|
| Vibrations at constant acceleration 2 g (IEC/EN 60068-2-6) |
57 Hz - 150 Hz
|
| Vibrations at constant amplitude .15 mm (IEC/EN 61131-2:2008) |
10 Hz - 57 Hz
|
| Ambient operating temperature - min |
-25 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
40 °C
|
| Drop height (IEC/EN 60068-2-31) |
50 mm
|
| EMC of electromagnetic fields rfi (IEC EN 61000-4-3) |
10 V/m
|
| EMC of electrostatic air discharge level 3 (IEC/EN 61000-4-2) |
8 KV
|
| Heat dissipation of power supply at 24 V DC |
4.8 W
|
| Bus addresses |
1 - 26 via DMI
|
| EMC of electrostatic contact discharge level 3 (IEC/EN 61000-4-2) |
6 KV
|
| Power supply admissable - max |
28.8 VDC
|
| Degree of protection |
IP20
|
| Protocol |
PROFIBUS-DP
PROFIBUS |
| Insulation resistance |
acc. to EN 50178
|
| Terminal capacity (cable) |
0.2 mm² - 2.5 mm² with ferrule
AWG 22 - AWG 12 with ferrule |
| Terminal capacity (solid wire) |
0.2 mm² - 4 mm² (AWG 22 - AWG 12)
|
| Functions |
Protection against polarity reversal, AS-I power supply
PROFIBUS-DP slave |
| Corrosion resistance |
1 cm³/m³ (4 days SO₂)
10 cm³/m³ (4 days SO₂) |
| Shock resistance |
18 impacts (IEC 60068-2-27)
|
| System accessory |
No
|
| Voltage dips |
10 ms
|
| Operating air pressure - max |
1080 hPa
|
| Operating air pressure - min |
795 hPa
|
| Packaged free fall height (IEC/EN 60068-2-32) |
1 m
|
| Power supply admissable - min |
20.4 VDC
|
| Tightening torque |
0.6 Nm
|
| Power supply status display |
Power LED (POW): green
|
| Relative humidity - max |
95 %
|
| Residual ripple - max |
5 %
|
| Rated current of power supply |
200 mA (24 V DC)
|
| Services (cyclic) |
Remote operator actuation, display/operation NZM-XDMI612 inputs/outputs, motor starter functions
Status ON/OFF/tripped (detailed), load early warnings, phase currents I1/I2/I3 [A] |
| EMC of power pulses/surge level 2 (IEC/EN 61000-4-5) |
0.5 kV (supply cables, symmetrical)
|