Eaton Distribution parts, FI-63/4/003-A. Residual current circuit-breaker, 63A, 4p, 03A, A-Char
| Product Name |
Eaton Distribution parts
|
| Catalog Number |
279221
|
| Product Length/Depth |
76 mm
|
| Product Height |
80 mm
|
| Product Width |
70 mm
|
| Product Weight |
0.351 kg
|
| Certifications |
IEC/EN 61008
|
| Amperage Rating |
63 A
|
| Voltage rating |
230 V AC / 400 V AC
|
| Features |
Residual current circuit breaker
Additional equipment possible |
| Fitted with: |
Interlocking device
|
| Frame |
45 mm
|
| Frequency rating |
50 Hz
|
| Pollution degree |
2
|
| Lifespan, mechanical |
20000 operations
|
| Mounting Method |
Top-hat rail IEC/EN 60715
DIN rail |
| Climatic proofing |
According to IEC/EN 61008
|
| Equipment heat dissipation, current-dependent |
13.4 W
|
| Rated impulse withstand voltage (Uimp) |
6 kV
4 kV |
| Admissible back-up fuse |
63 A gL (for In = 16 A - 63 A)
80 A gL (for In = 80 A) 100 A gL (for In = 100 A) |
| Rated short-time withstand current (Icw) |
10 kA
|
| Busbar material thickness |
0.8 mm - 2 mm
|
| Terminal protection |
Protection against electric shock to IEC 536
|
| Terminals (top and bottom) |
Twin-purpose terminals
|
| Ambient operating temperature - max |
60 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Built-in depth |
69.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
16 mm²
|
| Connectable conductor cross section (multi-wired) - min |
1.5 mm²
|
| Connectable conductor cross section (solid-core) - max |
35 mm²
|
| Connectable conductor cross section (solid-core) - min |
1.5 mm²
|
| Enclosure width |
80 mm
|
| Fault current rating |
30 mA
|
| Heat dissipation capacity |
0 W
|
| Heat dissipation per pole, current-dependent |
0 W
|
| Degree of protection |
IP20
IP40 |
| Impulse withstand current |
Partly surge-proof 250 A
|
| Number of poles |
Four-pole
|
| Leakage current type |
A
|
| Lifespan, electrical |
4000 operations
|
| Type |
|
| Special features |
Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
|
| Rated non-tripping current |
0.5 x I∆n
|
| Mounting width |
70 mm
|
| Sensitivity type |
DC and pulsed current
AC and pulsating DC current sensitive |
| Rated fault current - max |
0.03 A
|
| Rated fault current - min |
0.03 A
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational current for specified heat dissipation (In) |
63 A
|
| Rated operational voltage (Ue) - max |
400 V
|
| Rated switching capacity |
10 kA
|
| Static heat dissipation, non-current-dependent |
0 W
|
| Surge current capacity |
0.25 kA
|
| Voltage rating - max |
440 VAC
|
| Voltage rating - min |
184 VAC
|
| Width in number of modular spacings |
4
|
| Voltage type |
AC
|
| Terminal capacity (solid wire) |
1.5 mm² - 35 mm²
|
| Rated fault switching capacity |
1000 A (for In = 100 A)
630 A (for In = 63 A) 500 A (for In = 16 A - 40 A) 800 A (for In = 80 A) |
| Tripping time |
Non-delayed
|
| Rated short-circuit strength |
10 kA
|
| Terminal capacity (stranded cable) |
16 mm² (2x)
|
| RAL-number |
7035
|
| Color |
Gray
|