Reset
Eaton Moeller series xEffect - FAZ-HS MCB. FAZ-HS, 1-pole, tripping characteristic: B, rated current In: 4 A
| Product Name |
Eaton Moeller series xEffect - FAZ-HS MCB
|
| Catalog Number |
279274
|
| Product Length/Depth |
80 mm
|
| Product Height |
75.5 mm
|
| Product Width |
17.7 mm
|
| Product Weight |
0.112 kg
|
| Compliances |
RoHS conform
|
| Certifications |
CE marking
IEC/EN 60898 IEC/EN 60947-2 |
| Used with |
Miniature circuit breaker
FAZ-HS |
| Amperage Rating |
4 A
|
| Voltage rating |
240 V AC / 415 V AC
|
| Features |
Additional equipment possible
|
| Frame |
45 mm
|
| Pollution degree |
2
|
| Mounting Method |
Top-hat rail IEC/EN 60715
|
| Degree of protection |
IP40 (when fitted)
IP20 (IEC) UL/CSA Type: - IP20 |
| Rated impulse withstand voltage (Uimp) |
4 kV
|
| Admissible back-up fuse - max |
125 A gL/gG
|
| Busbar material thickness |
0.8 mm - 2 mm
|
| Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
| Terminals (top and bottom) |
Twin-purpose terminals
|
| Tripping characteristic |
B
|
| Voltage rating (UL CSA 13) |
277 V AC; 48 V DC
|
| Ambient operating temperature - max |
75 °C
|
| Ambient operating temperature - min |
-25 °C
|
| Built-in depth |
70.5 mm
|
| Connectable conductor cross section (multi-wired) - max |
25 mm²
|
| Connectable conductor cross section (multi-wired) - min |
1 mm²
|
| Connectable conductor cross section (solid-core) - max |
25 mm²
|
| Connectable conductor cross section (solid-core) - min |
1 mm²
|
| Current limiting class |
3
|
| Enclosure width |
80 mm
|
| Frequency rating - max |
60 Hz
|
| Frequency rating - min |
50 Hz
|
| Direction of incoming supply |
As required
|
| Width in number of modular spacings |
1
|
| Voltage rating at DC |
60 V DC (per pole)
|
| Voltage type |
AC
|
| Mounting position |
As required
|
| Overvoltage category |
III
|
| Number of poles |
Single-pole
|
| Lifespan, electrical |
10000 operations
|
| Release characteristic |
B
|
| Type |
|
| Application |
|
| Mounting width |
17.5 mm
|
| Selectivity class |
3
|
| Mounting width per pole |
17.5 mm
|
| Number of poles (protected) |
1
|
| Number of poles (total) |
1
|
| Operational switching capacity |
7.5 kA
|
| Rated insulation voltage (Ui) |
440 V
|
| Rated operational voltage (Ue) - max |
230 V
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1) - Icn at 230 V |
10 kA
|
| Rated short-circuit breaking capacity (IEC/EN 60898-1)- Icn at 400 V |
10 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V |
15 kA
|
| Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 400 V |
15 kA
|
| Rated switching capacity (IEC/EN 60947-2) |
10 kA
|
| Terminal capacity (control cable) |
25 mm² (1x)
|
| Terminal capacity of screw terminals for main cable |
10 mm² (2x)
|
| Power loss |
1.5 W
|