照片为代表
Download
Eaton Moeller® series P5 Auxiliary contact, 2N/O+1N/C, for P5, 125A, flush mounting
Product Name |
Eaton Moeller® series P5 Accessory Auxiliary contact
|
Catalog Number |
280963
|
Product Length/Depth |
50 mm
|
Product Height |
75 mm
|
Product Width |
130 mm
|
Product Weight |
0.045 kg
|
Compliances |
CE Marked
|
Certifications |
IEC 60947-5
UL 508 CSA Std. C22.2 No. 14-05 EN 60947-5 CSA File No.: 223805 CSA-C22.2 No. 14-05 CSA UL File No.: E36332 CSA Class No.: 3211-03 IEC/EN 60947-5 CE UL Category Control No.: NLRV, NLRV7 |
Catalog Notes |
Late-break switching-on behavior, early-make switching-off behavior
|
Used with |
P5-125(160)/E(EA)
|
Type |
Auxiliary contact
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Screw connection
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0.11 W
|
Number of contacts (change-over contacts) |
0
|
Number of contacts (normally closed contacts) |
1
|
Number of contacts (normally open contacts) |
2
|
Number of switches (fault signal) |
0
|
Mounting position |
Right side
Left side |
Connection type |
Screw connection
|
Mounting method |
Side mounting
|
Control circuit reliability |
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
|
Model |
Top mounting
|
Lamp holder |
None
|
Rated operational current (Ie) |
0.1 A at DC-13, 250 V
|
Rated uninterrupted current (Iu) |
10 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Stripping length (main cable) |
8 mm
|
Product category |
Accessories
|
Short-circuit protection rating |
Max. 10 A gG/gL, Fuse, Auxiliary contacts
|
Rated insulation voltage (Ui) |
500 V
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
6 A
|
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V |
3 A
|
Rated operational current (Ie) at DC-13, 125 V |
0.23 A
|
Rated operational current for specified heat dissipation (In) |
6 A
|
Terminal capacity (flexible with ferrule) |
0.5 - 2.5 mm², ferrules to DIN 46228
|
Terminal capacity (solid) |
0.5 - 2.5 mm²
|
Tightening torque |
0.8 Nm, Screw terminals
|