Eaton xComfort BF LV systems Final Distribution Boards. Complete surface-mounted flat distribution board, white, 24 SU per row, 3 rows, type P
| Product Name | 
                                                Eaton xComfort BF small distribution board
                                             | 
| Catalog Number | 
                                                285345
                                             | 
| Product Length/Depth | 
                                                150 mm
                                             | 
| Product Height | 
                                                610 mm
                                             | 
| Product Width | 
                                                555 mm
                                             | 
| Product Weight | 
                                                10.3 kg
                                             | 
| Compliances | 
                                                RoHS conform
                                             | 
| Certifications | 
                                                IEC/EN 61439-3  IEC/EN 62208 IEC/EN 61439-1 | 
| Special features | 
                                                IP30
Protection Class I
Steel sheet enclosure white (RAL 9016)
                                             | 
| Type | 
                                                Basic device
BF flat DBO
Installation distribution boards
                                             | 
| Features | 
                                                EMC-version  Earthing terminal block Neutral terminal block | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.13 Mechanical function | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Not relevant to indoor installations.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply to enclosures without lifting aids.
                                             | 
| 10.2.6 Mechanical impact | 
                                                IK07
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                IP30
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.5 Protection against electric shock | 
                                                < 0.1 Ω; meets the product standard's requirements.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Ui = 415 V AC
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Does not apply to basic enclosures as defined in EN 62208.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Does not apply to metal enclosures.
                                             | 
| Fitted with: | 
                                                Front plates  Door with three-point turn-lock Enclosure Neutral-/protective conductor terminal Cable gland plate inserts (top) DIN rail mounting frame | 
| Enclosure material | 
                                                Steel
                                             | 
| Built-in height | 
                                                610 mm
                                             | 
| Built-in width | 
                                                555 mm
                                             | 
| Cable entry postion | 
                                                Cable entries on top and bottom
                                             | 
| Terminal type | 
                                                Screw terminals
                                             | 
| Built-in depth | 
                                                150 mm
                                             | 
| Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) | 
                                                44 W
                                             | 
| Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) | 
                                                41 W
                                             | 
| Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) | 
                                                42 W
                                             | 
| Closure type | 
                                                Other
                                             | 
| Cover/door color | 
                                                White
                                             | 
| Cover/door model | 
                                                Closed
                                             | 
| Cover/door type | 
                                                Door  Single | 
| RAL-number | 
                                                9016
                                             | 
| Width in number of modular spacings | 
                                                24
                                             | 
| Ambient operating temperature details | 
                                                -5 °C - 40 °C
                                             | 
| Application | 
                                                Indoor (installation site)
                                             | 
| Voltage rating at AC | 
                                                415 V AC
                                             | 
| Color | 
                                                White  Traffic white (RAL 9016) | 
| Number of rows | 
                                                3
                                             | 
| Frequency rating of contacts | 
                                                50 Hz / 60 Hz
                                             | 
| Module rack type | 
                                                Rail frame
                                             | 
| Degree of protection | 
                                                IK07 (impact resistance)  IP30 | 
| Number of module space units per row | 
                                                24
                                             | 
| Protection class | 
                                                I (earthed)
                                             | 
| Protective shrouding material | 
                                                Metal
                                             | 
| Functions | 
                                                Basic device  Sealable | 
| Material | 
                                                Sheet steel, powder-coated
                                             | 
| Mounting method | 
                                                DIN-rail  Surface mounted (plaster) Surface mounting | 
| Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) | 
                                                89 W
                                             | 
| Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) | 
                                                81 W
                                             | 
| Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) | 
                                                85 W
                                             | 
| Internal depth | 
                                                131 mm
                                             | 
| PE and N terminal number and cross section | 
                                                PE: 2 x 25 mm² + 43 x 16 mm²  N: 2 x 25 mm² + 43 x 16 mm² | 
| Number of openings for socket outlets | 