Product Name |
Eaton Moeller series NZM Earth leakage relay
|
Catalog Number |
285557
|
Product Length/Depth |
80 mm
|
Product Height |
45 mm
|
Product Width |
95 mm
|
Product Weight |
0.192 kg
|
Compliances |
IEC
RoHS conform |
Certifications |
IEC 1009
IEC 1008 IEC 755 IEC/EN 60947-2 |
Features |
Sealable, setting buttons
1 integrated changeover contact (relay contact) |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Frame |
45 mm
NZM1/2/3/4 |
Mounting Method |
Snap fixing, top-hat rail DIN 46277, IEC/EN 60715
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Current rating of relay contact |
6 A
|
Device width |
85 mm
|
Power consumption |
3 W
|
Power on-delay time - max |
5000 ms
|
Power on-delay time - min |
5000 ms
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
276 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
184 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
276 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
184 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Terminal protection |
Finger/back-of-hand proof to BGV A2, VDE 106 part 100
|
Terminals (top and bottom) |
Box terminals
|
Voltage rating of relay contact |
250 V AC / 100 V DC
|
Delay time |
0.02, 0.1, 0.3, 0.5, 1, 3, 5 ms
|
Functions |
Delay adjustable
|
Terminal capacity (solid/flexible conductor) |
0.75 mm² - 1.5 mm² (2x) with ferrules
0.75 mm² - 2.5 mm² (2x) solid, 0.75 mm² - 1.5 mm² (2x) flexible/with ferrules |
Type |
|
Special features |
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated fault current - max |
5 A
|
Rated fault current - min |
0.03 A
|
Rated operating voltage (Ue) - max |
276 V
|
Sensitivity type |
Pulse current sensitive, type A
|