Eaton xEffect Accessories LV systems Accessories and replacement parts for LV switchgear. NH fuse base, 630A, 630A/500V, 500A/690V, NH3
Product Name |
Eaton xEffect Accessories fuse device NH fuse base
|
Catalog Number |
289018
|
Product Length/Depth |
133 mm
|
Product Height |
272 mm
|
Product Width |
254 mm
|
Product Weight |
3.035 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC/EN 60 269-2-1
VDE 0636-201 |
Used with |
Fuse bases
NH fuse base |
Amperage Rating |
630 A
|
Connection type |
Connector M10
|
Number of poles |
Three-pole
|
Voltage rating at AC |
Contacts: 690 V AC
|
Voltage rating at DC |
440 V DC
|
Rated current (gl/gG) - max |
630 A
|
Pollution degree |
3
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Screw diameter for flange connection |
M10
|
Admissible heat dissipation (NH-SE) - max |
48 W
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Heat dissipation at Ith AC without NH-SE |
52 W
|
Operating altitude without derating - max |
2000 mm
|
Rated insulation voltage (Ui) |
750 VAC
|
Bus-mounting type |
No
|
Direction of incoming supply |
As required
|
Construction size |
NH3
|
Mounting position |
Vertical or horizontal
|
Overvoltage category |
III
|
Frequency rating of contacts |
40 Hz - 60 Hz
|
Mounting method |
Screw
|
Degree of protection |
IP00
|
Rated operation current (Ie) |
630 A
|
Type |
|
Fuse current rating at 690 V - max |
500 A
|
Heat dissipation at Ith DC without NH-SE |
34.7 W
|
Terminal capacity (cable) |
21 mm x 1 mm (11x) at box terminal
|
Terminal capacity (copper busbar) |
Max. 40 mm x 10 mm for flat busbar at flange connection
|
Terminal capacity (flange connection) - max |
25 mm² - 300 mm² (1x) for cable lugs
|
Terminal capacity (stranded cable) |
120 mm² - 300 mm² at clamp-type terminal
120 mm² - 240 mm² (2x) at double clamp-type terminal 25 mm² - 300 mm² at box terminal |
Tightening torque |
30 Nm - 35 Nm
11 Nm |