下载文档 () / 20
已退市

289933

Eaton XIOC Analog input card for XC100/200, 24 V DC, 4AI(Thermoel.typ K,J,L,B,N,E,R,S,T)

常用规格

Product Name
Eaton XIOC Accessory Input card
Catalog Number
289933
Product Length/Depth
100 mm
Product Height
95 mm
Product Width
30 mm
Product Weight
0.115 kg
Certifications
CSA
UL Category Control No.: NRAQ
CSA-C22.2 No. 0-M
UL File No.: E135462
CSA-C22.2 No. 142-M
IEC/EN 61131-2
UL
CE
CSA Class No.: 2252-01
CSA File No.: 012528
EN 50178
UL508
Catalog Notes
Temperature measuring ranges: K type: -270 - 1370 °C, J type: -210 - 1200 °C, B type: 100 - 1800 °C, N type: -270 - 1300 °C, E type: -270 - 1000 °C, R type: -50 - 1760 °C, T type: -200 - 400 °C

产品规格

Used with
XC100/200 (expandable with up to 15 XI/OC modules)
Type
Analog module
Features
Input signal, configurable
Input, thermocouple
Analog outputs configurable
Analog inputs configurable
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Electric connection type
Screw-/spring clamp connection
Fitted with:
Cold junction compensation
Pollution degree
2
Resolution
16 Bit
Terminals
  • Optionally, screw terminals or spring-loaded terminals for digital/analog modules
  • Plug-in terminal block
Admissible range
20.4 – 28.8 V (11.8 – 14.4 V), Power supply
Power supply
24 V DC (-15/+20 %), approx. 150 mA
Explosion safety category for dust
None
Rated operational current for specified heat dissipation (In)
0 A
Repetition rate
1 s
Resolution of the analog inputs
16 Bit
Resolution of the analog outputs
0 Bit
Static heat dissipation, non-current-dependent Pvs
0.5 W
Input
4 Inputs (for thermocouples)
Explosion safety category for gas
None
Overvoltage category
II
Emitted interference
Class A (according to DIN/EN 55011/22)
Potential isolation
Analog inputs: Opto-isolated
Analog outputs: no
Power loss
Max. 4.8 W
Conversions
< 1 ms, Inputs
≤ 5 ms
Number of inputs (analog)
4
Protection class
1
Impact resistance
500 g/⌀ 50 mm ±25 g
Residual ripple
≤ 5 %
Rated operational voltage
24 (12) V DC
Degree of protection
IP20
Vibration resistance
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Voltage measurement
-500 - 500 mV
-1000 - 1000 mV
-50 - 50 mV
-100 - 100 mV
Total error
± 0.5 % of measurement range, Inputs
Voltage dips
10 ms
Safety performance level (EN ISO 13849-1)
None
SIL (IEC 61508)
None
Ambient operating temperature - max
55 °C
Ambient operating temperature - min
0 °C
Ambient storage temperature - max
70 °C
Ambient storage temperature - min
-25 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Number of outputs (analog)
0
Interference voltage suppression
50/60 Hz (Inputs)

导出产品规格