Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 385 A, 200 kW, IP00, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
3-4917-104A
|
Product Length/Depth |
561 mm
|
Product Height |
1538 mm
|
Product Width |
506 mm
|
Product Weight |
410 kg
|
Certifications |
UkrSEPRO
IEC/EN 61800-3 CUL RoHS, ISO 9001 UL Category Control No.: NMMS, NMMS7 EAC UL Specification for general requirements: IEC/EN 61800-2 UL File No.: E134360 CE Safety requirements: IEC/EN 61800-5 C-Tick |
Features |
Externally accessible fan
Temperature-controlled fan |
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
Fitted with: |
IGBT inverter
Radio interference suppression filter Internal DC link Additional PCB protection Multi-line graphic display Brake chopper DC link choke Breaking resistance Control unit PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
U/f control
Speed control with slip compensation Sensorless vector control (SLV) Torque regulation |
Frame size |
FS7
|
Air volume capacity |
1400 m³/h
|
Altitude |
Max. 1000 m
Max. 2000 m for Corner Grounded TN Systems Max. 3000 m Above 1000 m with 1 % derating per 100 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
318.7 kVA
|
Apparent power at 480 V |
398.4 kVA
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
437 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
353 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
65 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
108 W
|
Switch-on threshold for the braking transistor |
850 VDC
|
Voltage rating - max |
500 VAC
|
Overvoltage category |
III
|
Communication interface |
DeviceNet, optional
CANopen®, optional SmartWire-DT, optional Modbus TCP, built in BACnet MS/TP, built in Modbus RTU, built in Ethernet IP, built in PROFIBUS, optional |
Converter type |
U converter
|
Degree of protection |
IP00
NEMA Other |
Protocol |
BACnet
CAN DeviceNet EtherNet/IP MODBUS Other bus systems PROFIBUS PROFINET IO TCP/IP |
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
361 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
414 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
436 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
349 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz |
300 HP
|
Assigned motor power at 460/480 V, 60 Hz, 110% overload |
350 HP
|
Braking resistance |
1.4 Ω
|
Equipment heat dissipation, current-dependent Pvid |
5465 W
|
Input current ILN at 110% overload |
460 A
|
Input current ILN at 150% overload |
391 A
|
Mains current distortion |
28 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit |
Cable length |
50 m, screened, maximum permissible, Motor feeder
C3 ≤ 50 m, Radio interference level, maximum motor cable length C2 ≤ 10 m, Radio interference level, maximum motor cable length |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
480 V AC, 3-phase
500 V AC, 3-phase 400 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter, for conducted emissions only |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
97.9 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
385 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
200 kW
|
Output at quadratic load at rated output voltage - max |
250 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
506 A
|
Overload current IL at 150% overload |
577.5 A
|
Shock resistance |
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27 UPS drop test (for weights inside the UPS frame) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
2 kHz, 1.5 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
500 V AC, 3-phase
400 V AC, 3-phase 480 V AC, 3-phase |
Short-circuit protection rating |
600 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
460 A
|
Rated operational current (Ie) at 150% overload |
385 A
|
Rated operational current for specified heat dissipation (In) |
385 A
|
Rated operational power at 380/400 V, 50 Hz |
200 kW
|
Rated operational power at 380/400 V, 50 Hz, 110% overload |
250 kW
|
Rated operational power at 500 V, 50 Hz |
250 kW
|
Rated operational power at 500 V, 50 Hz, 110% overload |
315 kW
|
Safety function/level |