照片为代表
Download
Eaton DM1 Variable frequency drive, 230 V AC, 3-phase, 4.8 A, 1.1 kW, IP20/NEMA0, Brake chopper, FS1
Product Name |
Eaton DM1 Variable frequency drive
|
Catalog Number |
3-5018-007A
|
Product Length/Depth |
180 mm
|
Product Height |
152 mm
|
Product Width |
72 mm
|
Product Weight |
1.2 kg
|
Certifications |
UL Category Control No.: NMMS, NMMS7
CSA-C22.2 No. 274-17 UL report applies to both US and Canada CUL CE marking IEC/EN 61800-2 EAC IEC/EN 61800-3 UL File No.: E134360 UL Listed UkrSEPRO IEC/EN 61800-5-1 UL 508C IEC/EN61800-5 UL IEC/EN61800-3 CE RoHS, ISO 9001 Certified by UL for use in Canada C-Tick CSA-C22.2 No. 274-13 |
Product Category |
Variable frequency drives
|
Features |
Parameterization: Fieldbus
Parameterization: Keypad Temperature-controlled fan Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
IGBT inverter
Brake chopper Internal DC link PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Operating mode |
U/f control
|
Frame size |
FS1
|
Air volume capacity |
26 m³/h
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 3000 m Max. 1000 m Max. 2000 m for Corner Grounded TN Systems |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
4.2 A
|
Assigned motor current IM at 230 V, 50 Hz, 110% overload |
6.3 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
4.6 A
|
Assigned motor current IM at 230 V, 60 Hz, 110% overload |
6.8 A
|
Mains voltage tolerance |
200 - 240 V (-15 %/+10 %, at 50/60 Hz)
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Voltage rating - max |
240 V
|
Overvoltage category |
III
|
Communication interface |
DeviceNet, optional
SmartWire-DT, optional Modbus RTU, built in CANopen®, optional PROFIBUS, optional |
Converter type |
U converter
|
Degree of protection |
IP20
NEMA Other |
Protocol |
MODBUS
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
1 HP
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload |
2 HP
|
Braking resistance |
36 Ω
|
Equipment heat dissipation, current-dependent Pvid |
85 W
|
Input current ILN at 110% overload |
9.4 A
|
Input current ILN at 150% overload |
5.8 A
|
Mains current distortion |
40 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
1 (expansion)
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Adjustable to 150 %, DC - Main circuit Max. 30 % MN, Standard - Main circuit |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
230 V AC, 3-phase
240 V AC, 3-phase |
Number of inputs (analog) |
1
|
Number of inputs (digital) |
4
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter |
Number of outputs (digital) |
0
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
85 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
240 V
|
Mains voltage - min |
200 V
|
Nominal output current I2N |
4.8 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
0.75 kW
|
Output at quadratic load at rated output voltage - max |
1.1 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
240 V
|
Overload current IL at 110% overload |
8.58 A
|
Overload current IL at 150% overload |
7.2 A
|
Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
4 kHz, 1 - 16 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
230 V AC, 3-phase
240 V AC, 3-phase |
Short-circuit protection rating |
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
7.8 A
|
Rated operational current (Ie) at 150% overload |
4.8 A
|
Rated operational current for specified heat dissipation (In) |
7.8 A
|
Rated operational power at 220/230 V, 50 Hz, 1-phase |
1.1 kW
|
Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload |
1.5 kW
|
Heat dissipation at current/speed |
29 W at 25% current and 0% speed
31 W at 100% current and 50% speed 31 W at 25% current and 50% speed 38 W at 50% current and 50% speed 43 W at 50% current and 90% speed 50 W at 100% current and 0% speed 67 W at 50% current and 0% speed 84 W at 100% current and 90% speed |