Eaton S711 Soft starter, 320 A, 200 - 575 V AC, Us= 110-240 V AC, with control unit, Frame size 4, IP00
| Product Name | 
                                            
                                            
                                             
                                                Eaton S711 soft starter
                                             
                                         | 
                                    
| Catalog Number | 
                                            
                                            
                                             
                                                EP-401528
                                             
                                         | 
                                    
| Product Length/Depth | 
                                            
                                            
                                             
                                                545 mm
                                             
                                         | 
                                    
| Product Height | 
                                            
                                            
                                             
                                                204 mm
                                             
                                         | 
                                    
| Product Width | 
                                            
                                            
                                             
                                                222 mm
                                             
                                         | 
                                    
| Product Weight | 
                                            
                                            
                                             
                                                19.63 kg
                                             
                                         | 
                                    
| Certifications | 
                                            
                                            
                                             
                                                CE  
                                        RCM IEC/EN 60947-4-2 CUL UL UL Category Control No.: NMFT UL Category Control No.: NMFT7 UL File No.: E251034 UL 60947-4-2  | 
                                    
| Type | 
                                            
                                            
                                             
                                                Soft starter for three-phase loads, with control unit and pump algorithm, DC Brake, Soft Brake, Jog, Bluetooth
                                             
                                         | 
                                    
| 10.10 Temperature rise | 
                                            
                                            
                                             
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             
                                         | 
                                    
| 10.11 Short-circuit rating | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             
                                         | 
                                    
| 10.12 Electromagnetic compatibility | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             
                                         | 
                                    
| 10.13 Mechanical function | 
                                            
                                            
                                             
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             
                                         | 
                                    
| 10.2.2 Corrosion resistance | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.2.5 Lifting | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.2.6 Mechanical impact | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.2.7 Inscriptions | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.3 Degree of protection of assemblies | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.4 Clearances and creepage distances | 
                                            
                                            
                                             
                                                Meets the product standard's requirements.
                                             
                                         | 
                                    
| 10.5 Protection against electric shock | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.6 Incorporation of switching devices and components | 
                                            
                                            
                                             
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             
                                         | 
                                    
| 10.7 Internal electrical circuits and connections | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.8 Connections for external conductors | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.9.2 Power-frequency electric strength | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.9.3 Impulse withstand voltage | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| 10.9.4 Testing of enclosures made of insulating material | 
                                            
                                            
                                             
                                                Is the panel builder's responsibility.
                                             
                                         | 
                                    
| Fitted with: | 
                                            
                                            
                                             
                                                Display  
                                        Motor overload protection Internal bypass  | 
                                    
| Pollution degree | 
                                            
                                            
                                             
                                                3
                                             
                                         | 
                                    
| Class | 
                                            
                                            
                                             
                                                Adjustable (5,10,15,20,30)
                                             
                                         | 
                                    
| Climatic proofing | 
                                            
                                            
                                             
                                                5 to 95% Relative Humidity
                                             
                                         | 
                                    
| Connection to SmartWire-DT | 
                                            
                                            
                                             
                                                No
                                             
                                         | 
                                    
| Rated impulse withstand voltage (Uimp) | 
                                            
                                            
                                             
                                                6000 V
                                             
                                         | 
                                    
| Frame size | 
                                            
                                            
                                             
                                                FS4
                                             
                                         | 
                                    
| Altitude | 
                                            
                                            
                                             
                                                Max 4000 m (Above 1000 m for detailed derating use S711 Select Software)
                                             
                                         | 
                                    
| Number of inputs | 
                                            
                                            
                                             
                                                5 (2 fixed, 2 programmable, 1 thermistor)
                                             
                                         | 
                                    
| Ambient operating temperature - max | 
                                            
                                            
                                             
                                                60 °C
                                             
                                         | 
                                    
| Ambient operating temperature - min | 
                                            
                                            
                                             
                                                -25 °C
                                             
                                         | 
                                    
| Ambient storage temperature - max | 
                                            
                                            
                                             
                                                70 °C
                                             
                                         | 
                                    
| Ambient storage temperature - min | 
                                            
                                            
                                             
                                                -40 °C
                                             
                                         | 
                                    
| Assigned motor power at 200/208 V, 60 Hz, 3-phase | 
                                            
                                            
                                             
                                                100 HP
                                             
                                         | 
                                    
| Assigned motor power at 220/230 V, 60 Hz, 3-phase | 
                                            
                                            
                                             
                                                100 HP
                                             
                                         | 
                                    
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 
                                            
                                            
                                             
                                                250 HP
                                             
                                         | 
                                    
| Assigned motor power in-delta at 220/230 V, 60 Hz | 
                                            
                                            
                                             
                                                150 HP
                                             
                                         | 
                                    
| Assigned motor power in-delta at 460/480 V, 60 Hz | 
                                            
                                            
                                             
                                                350 HP
                                             
                                         | 
                                    
| Assigned motor power in-delta at 575/600 V, 60 Hz | 
                                            
                                            
                                             
                                                450 HP
                                             
                                         | 
                                    
| Equipment heat dissipation, current-dependent Pvid | 
                                            
                                            
                                             
                                                1440 W
                                             
                                         | 
                                    
| Heat dissipation capacity Pdiss | 
                                            
                                            
                                             
                                                0 W
                                             
                                         | 
                                    
| Heat dissipation per pole, current-dependent Pvid | 
                                            
                                            
                                             
                                                0 W
                                             
                                         | 
                                    
| Mains voltage - max | 
                                            
                                            
                                             
                                                632.5 V
                                             
                                         | 
                                    
| Mains voltage - min | 
                                            
                                            
                                             
                                                170 V
                                             
                                         | 
                                    
| Output voltage | 
                                            
                                            
                                             
                                                250 V AC (relay outputs)
                                             
                                         | 
                                    
| Number of outputs | 
                                            
                                            
                                             
                                                3 Relay Outputs (1 fixed, 2 programmable)
                                             
                                         | 
                                    
| Screwdriver size | 
                                            
                                            
                                             
                                                17 mm M10, Terminal screw, Main cables  
                                        0.6 x 3.5 mm or PH0, Terminal screws, Control circuit cables  | 
                                    
| Voltage type | 
                                            
                                            
                                             
                                                AC
                                             
                                         | 
                                    
| Rated operational voltage (Ue) - min | 
                                            
                                            
                                             
                                                200 V
                                             
                                         | 
                                    
| Rated operational voltage (Ue) at AC - max | 
                                            
                                            
                                             
                                                575 V
                                             
                                         | 
                                    
| Rated power three-phase motor, inline, at 230 V | 
                                            
                                            
                                             
                                                90 kW
                                             
                                         | 
                                    
| Rated power three-phase motor, inline, at 400 V | 
                                            
                                            
                                             
                                                160 kW
                                             
                                         | 
                                    
| Rated power three-phase motor, inside delta, at 230 V | 
                                            
                                            
                                             
                                                150 kW
                                             
                                         | 
                                    
| Rated power three-phase motor, inside delta, at 400 V | 
                                            
                                            
                                             
                                                250 kW
                                             
                                         | 
                                    
| Static heat dissipation, non-current-dependent Pvs | 
                                            
                                            
                                             
                                                140 W
                                             
                                         | 
                                    
| Voltage rating - max | 
                                            
                                            
                                             
                                                575 V
                                             
                                         | 
                                    
| Application | 
                                            
                                            
                                            
  | 
                                    
| Protection | 
                                            
                                            
                                             
                                                Optional terminal cover for Finger and back-of-hand proof, Protection against direct contact
                                             
                                         | 
                                    
| Assigned motor power at 575 V_ 60 Hz_ 3-phase | 
                                            
                                            
                                             
                                                300 HP
                                             
                                         | 
                                    
| Mounting position | 
                                            
                                            
                                             
                                                As required
                                             
                                         | 
                                    
| Drop-out voltage | 
                                            
                                            
                                             
                                                0 - 90 V, AC operated
                                             
                                         | 
                                    
| Degree of protection | 
                                            
                                            
                                             
                                                IP00  
                                        NEMA Other  | 
                                    
| Current consumption | 
                                            
                                            
                                             
                                                600 mA, Control circuit, Digital inputs
                                             
                                         | 
                                    
| Functions | 
                                            
                                            
                                             
                                                Single direction  
                                        Torque control DC-Brake Soft-Brake Forward & reverse jog  | 
                                    
| Delay time | 
                                            
                                            
                                             
                                                0 - 180 s, Soft start function, Ramp times; 0 - 240 s, Soft stop function, Stop times
                                             
                                         | 
                                    
| Overload cycle | 
                                            
                                            
                                             
                                                AC-53b: 3.5-20:580
                                             
                                         | 
                                    
| Pick-up voltage | 
                                            
                                            
                                             
                                                93.5 - 264.0 V AC
                                             
                                         | 
                                    
| Radio interference class | 
                                            
                                            
                                             
                                                Class A (IEC 60947-4-2)
                                             
                                         | 
                                    
| Fault memory | 
                                            
                                            
                                             
                                                1000 Faults
                                             
                                         | 
                                    
| Interfaces | 
                                            
                                            
                                             
                                                Modbus RTU (built-in)  
                                        Bluetooth (built-in)  | 
                                    
| Kickstart | 
                                            
                                            
                                             
                                                600% (Kickstart current)  
                                        Max. 2000 ms (Kickstart Duration)  | 
                                    
| Rated control voltage (Uc) | 
                                            
                                            
                                             
                                                110 - 240 V AC (-15%/+10%)
                                             
                                         | 
                                    
| Supply frequency | 
                                            
                                            
                                             
                                                50/60 Hz, fLN, Main circuit
                                             
                                         | 
                                    
| Terminal capacity (stranded) | 
                                            
                                            
                                             
                                                1 x  (185 - 400) mm², Main cables  
                                        1x (1 - 2.5) mm², Control circuit cables  | 
                                    
| Rated control supply voltage (Us) at AC, 50 Hz - max | 
                                            
                                            
                                             
                                                240 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at AC, 50 Hz - min | 
                                            
                                            
                                             
                                                110 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at AC, 60 Hz - max | 
                                            
                                            
                                             
                                                240 V
                                             
                                         | 
                                    
| Rated control supply voltage (Us) at AC, 60 Hz - min | 
                                            
                                            
                                             
                                                110 V
                                             
                                         | 
                                    
| Rated insulation voltage (Ui) | 
                                            
                                            
                                             
                                                600 V
                                             
                                         | 
                                    
| Rated operational current (Ie) at AC-11 | 
                                            
                                            
                                             
                                                3 A
                                             
                                         | 
                                    
| Rated operational current (Ie) at AC-53 | 
                                            
                                            
                                             
                                                320 A
                                             
                                         | 
                                    
| Rated operational current (Ie) at AC-53, in-delta | 
                                            
                                            
                                             
                                                480 A
                                             
                                         | 
                                    
| Rated operational current for specified heat dissipation (In) | 
                                            
                                            
                                             
                                                320 A
                                             
                                         | 
                                    
| Rated operational power at 220/230 V, 50 Hz | 
                                            
                                            
                                             
                                                90 kW
                                             
                                         | 
                                    
| Rated operational power at 400 V, 50 Hz | 
                                            
                                            
                                             
                                                160 kW
                                             
                                         | 
                                    
| Rated operational power at 500 V, 50 Hz | 
                                            
                                            
                                             
                                                220 kW
                                             
                                         | 
                                    
| Rated operational power in-delta at 220/230 V, 50 Hz | 
                                            
                                            
                                             
                                                150 kW
                                             
                                         | 
                                    
| Rated operational power in-delta at 400 V, 50 Hz | 
                                            
                                            
                                             
                                                250 kW
                                             
                                         | 
                                    
| Rated operational power in-delta at 500 V, 50 Hz | 
                                            
                                            
                                             
                                                315 kW
                                             
                                         | 
                                    
| Rated operational voltage (Ue) - max | 
                                            
                                            
                                             
                                                575 V
                                             
                                         | 
                                    
| Ramp/run-up time | 
                                            
                                            
                                             
                                                180 s
                                             
                                         | 
                                    
| Shock resistance | 
                                            
                                            
                                             
                                                15 g, Mechanical
                                             
                                         | 
                                    
| Suitable for | 
                                            
                                            
                                             
                                                Branch circuits, not as BCPD, (UL/cUL)
                                             
                                         | 
                                    
| Tightening torque | 
                                            
                                            
                                             
                                                0.5 Nm, Screw terminals, Control circuit cables  
                                        40 Nm, Main cables  | 
                                    
| Short-circuit protection rating | 
                                            
                                            
                                             
                                                400NHG3B or NZMH3-A4008T, Type "1" coordination, Main conducting paths  
                                        170M6008 "Type 2" coordination, Main conducting paths  | 
                                    
| Start voltage | 
                                            
                                            
                                             
                                                Max. 600% FLA, Min. 100% FLA, Soft start function
                                             
                                         | 
                                    
| Startup class | 
                                            
                                            
                                             
                                                CLASS 20 (heavy starting duty 3 x Iₑ for 45 s)  
                                        CLASS 10 (star-delta replacement) CLASS 30 (6 x Iₑ for 30 s)  | 
                                    
| Terminal capacity (flexible with ferrule) | 
                                            
                                            
                                             
                                                1 x  (185 - 400) mm², Main cables  
                                        1x (1 - 2.5) mm², Control circuit cables  | 
                                    
| Terminal capacity (solid) | 
                                            
                                            
                                             
                                                1 x  (185 - 400) mm², Main cables  
                                        1x (1 - 2.5) mm², Control circuit cables  | 
                                    
| Terminal capacity (solid/stranded AWG) | 
                                            
                                            
                                             
                                                1 x  (350 - 750), Main cables  
                                        1x (28 - 12) , Control circuit cables  |