| Product Name |
Eaton Tripp Lite series SmartPro UPS
|
| Catalog Number |
SMX1500XLRT2U
|
| UPC |
037332119216
|
| Product Length/Depth |
23.3 in
|
| Product Height |
8.8 in
|
| Product Width |
19.9 in
|
| Product Weight |
43.1 lb
|
| Compliances |
CE Marked
RoHS EAC |
| Certifications |
AS/NZS 4417
GoST-R |
| Topology |
Line-interactive
|
| Rack size |
2U
|
| VA rating |
1500 VA
|
| Package contents |
|
| Nominal frequency |
50/60 Hz
|
| Input frequency range |
50/60 Hz
|
| Receptacle |
C13
|
| Output nominal voltage |
208V default (200/208/220/230/240V)
|
| Electric current - max |
10A
|
| Runtime graph |
|
| Battery replacement |
Pre-December 2023: RBC93-2U
Post-January 2024: 744-A4801
|
| Battery type |
Valve Regulated Lead Acid (VRLA)
|
| Extended battery capability |
Extended runtime supported via optional 48VDC BP48VRM2U external battery packs only.
|
| Runtime at half load |
14 min
|
| Noise level |
45 dBA maximum, front side 1m
|
| Relative humidity |
20-95% non-condensing
|
| Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
|
| Input Plug Type |
C14
|
| Output Receptacles |
C13
|
| Output Receptacles Details |
Compatible with Eaton Tripp Lite Power Cords
|
| Product Features |
Expandable Runtime
Individually Controllable Load Banks Emergency Power Off (EPO)/Remote On-Off (ROO) |
| Product Highlights |
2-line front-panel LCD with 10 selectable screens reports detailed UPS and site power info
2 year warranty, 3 year with registration. (Worldwide) Note: Registration is required for 3 year warranty. ENERGY STAR 2.0-certified to save electricity, lower costs and protect the environment Protects equipment against blackouts, brownouts, transient surges and line noise Keeps equipment running during outages to allow time for file saves and safe shutdown Unity power factor ensures maximum power possible at each power rating |
| PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Office software at https://tripplite.eaton.com/poweralert
|
| Nominal Output Voltage |
200V
208V 220V 230V 240V |
| Network Management Cards |
WEBCARDLXE
|
| Network Management Cards Details |
One slot for optional WEBCARDLXE web card. Note: Not compatible with WEBCARDLX
|
| Output power factor |
1
|
| Phase (input) |
Single-phase
|
| Runtime at full load |
5 min. (1500W)
|
| Communication interface |
Contact closure
USB (HID enabled) DB9 Serial EPO (emergency power off) Slot for SNMP / Web interface USB and DB9 serial cables included |
| Battery Access |
Front panel battery access door
|
| Typical Battery Runtime |
Expandable Runtime
|
| Dc Voltage |
48
|
| Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
| Communications Cable |
USB and DB9 cabling included
|
| Grounding Details |
Rear panel grounding lug
|
| Included Output Power Cables |
Set of 2 C13 to C14 power cables included
|
| Optional Mounting Accessory Notes |
Optional 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm)
|
| Load Management Receptacles |
Two switchable two-outlet C13 load banks
|
| High Voltage Transfer to Battery Power |
294V (Normal/Extended Modes)
|
| Low Voltage Transfer to Battery Power |
160V (Normal mode), 150V (Extended Mode)
|
| Undervoltage Correction |
Increases incoming voltage between 162-184V (Normal Mode) or 151-184V (Extended Mode) by 15%
|
| Network UPS Tools (NUT) Compatibility |
NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite
|
| Application |
|
| Switch configuration |
5 pushbutton switches control OFF / ON power status, ENTER, UP, and DOWN selection and ESC control functions
|
| Hot Swap PDU Options |
PDUBHV10 (2U / 8 C13 outlets)
|
| AC suppression joule rating |
175
|
| Housing material |
Steel
|
| Output AC waveform (AC mode) |
Pure Sine wave
|
| Output AC waveform (battery mode) |
Pure Sine wave
|
| Output Capacity (kVA) |
1.5
|
| Output Capacity (Watts) |
1500
|
| Operating Elevation |
|
| Primary UPS Depth (mm) |
447
|
| Primary UPS Height (mm) |
86
|
| Primary UPS Width (mm) |
437
|
| AC Suppression Response Time |
Instantaneous
|
| Alarm Interface |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
|
| Audible Alarms |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
|
| Battery Start Capability |
Cold-start operation supported
|
| Cooling Method |
Fan
|
| Battery Replacement Description |
Hot-swappable, user replaceable batteries
|
| Frequency Rating Details |
Automatic frequency selection
|
| Minimum Required Rack Depth With External Battery Pack |
21
|
| Minimum Required Rack Depth Without External Battery Pack |
21
|
| Output Voltage Regulation (Line Mode) |
208V (-13%, +15%)
|
| Output Voltage Regulation(Battery Mode) |
-10%, +6%
|
| Overvoltage Correction |
Reduces incoming voltage between 265-294V (Normal Mode / Extended Mode) by 13%
|
| Rechargeable Battery |
Less than 4.5 hours from 10% to 90% (typical, full load discharge)
|
| Storage Temperature |
5° to 122°F (-15° to 50°C)
|
| Form factor |
Rackmount
Tower |
| Included Mounting Accessory Description |
Included 4-post mounting kit enables installation in 4 post racks. Two ABS mounting stands enables the UPS to be configured in an upright tower orientation.
|
| Input Connection Description |
IEC320-C14 input connection accepts a variety of detachable cordsets to match country or site-specific wall receptacles
|
| Network Monitoring Port Description |
Network Card Optional. Not compatible with WEBCARDLX.
|
| Nominal Voltage Details |
208V nominal output in battery mode
|
| Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 150 to 294
|
| Maximum Input Amps |
10
|
| Minimum Required Rack Depth (cm) |
53.34
|
| Minimum Required Rack Depth (inches) |
21
|
| UPS Power Module Dimensions |
3.4 x 17.2 x 17.6
|
| Power Mode Transfer Time |
1-4ms for normal mode, >5ms for sensitive mode
|
| Optional Accessories |
2 post rackmount (103007018-5591)
|
| EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
| UPS Input Connection Type |
C14 inlet
|
| External Battery Pack Compatibility |
BP48VRM2U (limit 4)
|
| Green Energy-Saving Features |
Greater than 95% efficiency - GREEN UPS
Individually controllable load banks |
| Input Nominal Voltage |
200 VAC
208 VAC 220 VAC 230 VAC 240 VAC |
| High Availability UPS Features |
Surge/noise protection
Hot swappable batteries |
| Nominal Input Voltage Supported |
200 VAC
208 VAC 220 VAC 230 VAC 240 VAC |