下载文档 () / 20
动力,因我们而不同*

SUINT2200LCD2U

Tripp Lite series SmartOnline 2200VA 2000W 208/230V Double-Conversion UPS - 10 Outlets, Extended Run, Network Card Option, LCD, USB, DB9, 2U Rack/Tower

常用规格

Product Name
Eaton Tripp Lite series SmartOnline UPS
Catalog Number
SUINT2200LCD2U
UPC
037332183330
Product Length/Depth
23.82 in
Product Height
3.41 in
Product Width
17.33 in
Product Weight
59.75 lb
Warranty
2 year limited
Compliances
ENERGY STAR certified
RoHS
CE Marked
FCC Compliant
REACH
Certifications
UL 1778
CSA certified
CSA 22.2
cTUVus
NOM

产品规格

Topology
Online/Double-conversion
Rack size
2U
Color
Black
VA rating
2200 VA
Wattage
2000 W
Package contents
  • 2200VA 2000W 208/230V Double-Conversion UPS
  • Detachable C19 to L6-20P 16A power cord, 6 ft. (1.8 m)
  • USB cable
  • DB9 cable
  • (2) IEC 10A 6ft. output cables
  • Rack-mounting hardware
  • Tower support stands
  • Safety instructions
  • Quick start guide
Surge protection
Yes
Internal bypass
Yes
Current Crest Ratio
3:1
Input connection
C20
Input cord length
6 ft
Nominal frequency
50/60 Hz
Input frequency range
50/60 Hz
Input power factor
.99
Receptacle
(8) C13; (2) C19
Number of Outputs C13
8
Number of Outputs C19
2
Output waveform
True sine wave
Runtime graph
View runtime graph
Battery replacement
EBP-1616 *Note: EBP-1616 is the replacement battery for the SUINT2200LCD2U 2023 UPS design update featured on this page. For the replacement battery in the previous design of SUINT2200LCD2U, please see part number RBC48S
Battery type
Valve Regulated Lead Acid (VRLA)
Extended battery capability
  • Add up to 4 EBMs
  • Part number BP72RT
Standard factory warranty
2-year limited
Extended service plans
  • 5-year depot exchange plan: TL9SW5Y-2200UC
  • Parts, electronics and UPS batteries coverage
  • Next business day shipping
  • Technical support
  • 5-year onsite plan: TLWFLN75XX-2509UC
  • Onsite parts and labor coverage for 5 years
  • Parts, electronics and UPS batteries coverage
  • 24x7 onsite labor coverage, next-day response
  • Next-day shipping
  • Technical support
Runtime at half load
16.6 min
Communication
  • (1) WEBCARDLXE port
  • (1) USB port
  • (1) Serial RS-232 port
  • (1) RPO/ROO terminal
  • (1) mini-terminal block for output relay
Expansion slots
  • (1) WEBCARDLXE expansion port
  • Not compatible with WEBCARDLX
Includes network card
No
User interface
LCD display
Relative humidity
0-96% non-condensing
Temperature range
0° to 40°C (32° to 104°F)
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options
Runtime graph
Input Plug Type
C20
Output Receptacles
C13
C19
Output Receptacles Details
Compatible with Eaton Tripp Lite Power Cords
Product Features
Individually Controllable Load Banks
Expandable Runtime
L6-20P
Emergency Power Off (EPO)/Remote On-Off (ROO)
Product Highlights
2-year limited warranty (Worldwide)
Updated design for 2023
Optional WEBCARDLXE network card enables full remote access and control
Zero transfer time between on-line and battery modes for uninterrupted operation
Menu-driven LCD keeps you up to date with status info and other vital analytics
Keeps equipment running during outages to allow time for file saves and safe shutdown
Protects equipment against blackouts, brownouts, transient surges and line noise
PowerAlert Software
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
Nominal Output Voltage
200V
208V
220V
230V
240V
Network Management Cards
WEBCARDLXE
Network Management Cards Details
Network management card optional
Output power factor
0.9
Phase (input)
Single-phase
Runtime at full load
6 min. (2000W)
Communication interface
RS-232
USB
Contact closure
Slot for SNMP / Web interface
Battery Access
Battery access door
Typical Battery Runtime
Expandable Runtime
Dc Voltage
72
Operating Temperature Range
32° to 104°F (0° to 40°C)
Communications Cable
USB and RS232 cable included
Included Output Power Cables
(2) IEC 10A 6ft. output cables
Optional Mounting Accessory Notes
2 post rail kit available, part # RK2PC
Load Management Receptacles
Two switchable load banks. Group 1: Two C13 outlets plus one C19 outlet; Group 2: Two C13 outlets.
Application
Mission Critical Applications
Switch configuration
RPO / ROO
AC suppression joule rating
296
Housing material
Metal
Output AC waveform (AC mode)
Pure Sine wave
Output AC waveform (battery mode)
Pure sine wave
Output Capacity (kVA)
2.2
Output Capacity Details
220/230/240V: 2200VA / 2200W; 208V(default)/200V: 2200VA / 2000W
Operating Elevation
Up to 3000m
AC Suppression Response Time
Instantaneous
Alarm Interface
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
Audible Alarms
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Battery Start Capability
Cold-start operation supported
Cooling Method
Fan
Battery Replacement Description
Hot-swappable, user replaceable batteries
LED Indicators
4 status-indicating LEDs
Frequency Rating Details
Online Mode: Sync with line ±5% of nominal line frequency (outside this range: ±0.5% of auto-selected nominal frequency). Battery Mode: ±0.5% of auto-selected nominal frequency
Output Voltage Regulation (Economy Line Mode)
+/- 1%
Output Voltage Regulation (Line Mode)
+/- 1%
Output Voltage Regulation(Battery Mode)
+/- 2%
Rechargeable Battery
3 hours recharge to 90%
Recommended Electrical Service
208V
Storage Temperature
With battery: 32° to 104°F (0° to 40°C); without battery: -13° to 131°F (-25° to 55°C)
Form factor
Rackmount
Included Mounting Accessory Description
Includes 4 post rackmount and tower pedestal accessories
Input Current
10.57A
Input Nominal Voltage Description
208V factory default
Network Monitoring Port Description
WEBCARDLXE Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; not compatible with WEBCARDLX
Nominal Voltage Details
208V default
Voltage Regulation Description
Online, double-conversion power conditioning
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Plug Type
NEMA L6-20P
Maximum Input Amps
11
Minimum Required Rack Depth (cm)
68.07
Minimum Required Rack Depth (inches)
26.8
UPS Input Cord Length (m)
1.8
Power Mode Transfer Time
0 ms.
Output Capacity (VA)
2200
Optional Accessories
2 post rackmount (RK2PC)
EMI AC Noise Suppression
EMI / RFI AC Noise Suppression
UPS Input Connection Type
C20 inlet
External Battery Pack Compatibility
BP72RT
Green Energy-Saving Features
High efficiency economy mode operation
Individually controllable load banks
Input Nominal Voltage
200 VAC
208 VAC
220 VAC
230 VAC
240 VAC
High Availability UPS Features
Hot swappable batteries
Surge/noise protection
Expandable battery backup
Pure sine wave output
Remote management
Zero transfer time
On-Line/Double-Conversion

导出产品规格