Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 125A, plug-in module, B2-A125-SVE
Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
Catalog Number |
113192
|
Product Length/Depth |
180 mm
|
Product Height |
245 mm
|
Product Width |
105 mm
|
Product Weight |
2.8 kg
|
Compliances |
RoHS conform
|
Certifications |
IEC
|
Amperage Rating |
125 A
|
Voltage rating |
440 V - 440 V
|
Features |
Motor drive optional
Protection unit |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Mounting Method |
Built-in device plug-in technique
DIN rail (top hat rail) mounting optional Plug-in unit |
Equipment heat dissipation, current-dependent |
27.61 W
|
Ambient operating temperature - max |
70 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
40 °C
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Degree of protection |
IP20
|
Electrical connection type of main circuit |
Screw connection
|
Number of poles |
Three-pole
|
Special features |
Rated current = rated uninterrupted current: 125 A
|
Position of connection for main current circuit |
Front side
|
Power loss |
27.6 W
|
Short-circuit release non-delayed setting - max |
1250 A
|
Short-circuit release non-delayed setting - min |
750 A
|
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
1250 A
|
Instantaneous current setting (Ii) - min |
750 A
|
Overload current setting (Ir) - max |
125 A
|
Overload current setting (Ir) - min |
100 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
Standard terminals |
Screw terminal
|