下载文档 () / 20

118706

Eaton ESR5 Contact expansion module, 24VDC/AC, 4 enabling paths off-delayed

常用规格

Product Name
Eaton ESR5 Contact expansion module
Catalog Number
118706
Product Length/Depth
114.5 mm
Product Height
99 mm
Product Width
22.5 mm
Product Weight
0.173 kg
Certifications
UL File No.: E29184
Certified by UL for use in Canada
CSA Class No.: 3211-83; 3211-03
UL
2014/30/EU
IEC 62061
UL 508
IEC/EN 60204
EN 50178
CE
UL report applies to both US and Canada
UL Category Control No.: NKCR; NKCR7
EN ISO 13849-1
CSA-C22.2 No. 14-95
IEC 61508, Parts 1-7
Machines 2006/42/EG
Catalog Notes
The base unit determines the maximum stop category according to IEC 61508 and IEC 60204

产品规格

Type
Contact expansions
Mounting method
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Operating temperature - max
55 °C
Operating temperature - min
-20 °C
Features
Feedback current path
Safe insulation
6 kV between input circuit / NC contacts, and enable current paths
Basic insulation
Reinforced insulation
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Electric connection type
Screw connection
Fitted with:
Approval for TÜV
Detachable clamps
Approval according to UL
Feedback circuit
Pollution degree
2
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Rated impulse withstand voltage (Uimp)
4000 V AC
Air pressure
795 - 1080 hPa (operation)
Altitude
Max. 2000 m
Category (EN 954-1)
3
Degree of protection
IP20
Installation location: ≥ IP54
Enclosure: IP20
Terminals: IP20
Environmental conditions
Condensation: Non-condensing
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 14-95
Number of inputs
1-channel
Functions
1-channel
Time function
Safety performance level (EN ISO 13849-1)
Level d
Ambient operating temperature - max
55 °C
Ambient operating temperature - min
-20 °C
Ambient storage temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Nominal current
84 A
Number of outputs (safety related, delayed) with contact
4
Number of outputs (safety related, delayed, semiconductors)
0
Number of outputs (safety related, undelayed) with contact
0
Number of outputs (safety related, undelayed, semiconductors)
0
Number of outputs (signaling function, delayed) with contact
1
Number of outputs (signaling function, delayed, semiconductors)
0
Number of outputs (signaling function, undelayed) with contact
0
Number of outputs (signaling function, undelayed, semiconductors)
0
Rated control supply voltage (Us) at AC, 50 Hz - max
26.4 V
Rated control supply voltage (Us) at AC, 50 Hz - min
0 V
Rated control supply voltage (Us) at AC, 60 Hz - max
26.4 V
Screwdriver size
0.6 x 3.5 mm, Terminal screws
2, Terminal screw, Pozidriv screwdriver
Voltage type
DC
Connection type
M3 screw terminals
Mounting position
As required
Breaking power
1500 VA max., Output data, resistive load (τ = 0 ms), at 250 V AC (for N/C contacts 65 - 66)
288 W max., Output data, resistive load (τ = 0 ms), at 48 V DC (for N/C contacts 65 - 66)
40 W max., Output data, inductive load (τ = 40 ms), at 48 V DC
35 W max., Output data, inductive load (τ = 40 ms), at 110 V DC
144 W max. resistive load (τ = 0 ms), at 24 V DC (for N/C contacts 65 - 66)
33 W max., Output data, inductive load (τ = 40 ms), at 220 V DC
77 W max., Output data, resistive load (τ = 0 ms), at 110 V DC
88 W max., Output data, resistive load (τ = 0 ms), at 220 V DC
48 W max., Output data, inductive load (τ = 40 ms), at 24 V DC
Overvoltage category
III
Short-circuit protection rating
10A gL/gG, NEOZED (N/O), Output fuse, External, Output data
4A gL/gG, NEOZED (N/C), Output fuse, External, Output data
Duty factor
100 %
Off-delay
0.3 - 3 s (± 50 %)
Emitted interference
According to EN 61000-6-4
Current consumption
94 mA, DC
94 mA, AC
Material
Contacts: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Enclosure: Polyamide (PA), not reinforced
Interference immunity
According to EN 61000-6-2
Tightening torque
0.6 Nm, Screw terminals
Mounting width
22.5 mm
Suitable for
Safety relay contact expansion block per DIN EN60204-1/VDE 0113 Part 1 for contact multiplication
Monitoring of position switches
Monitoring of emergency-stop circuits
The expansion unit can be used for contact multiplication for emergency stop relays and two-hand controls
Relative humidity
< 75 %
LED indicator
Status indication of SmartWire-DT network: Green LED
Feedback current path
Delayed feedback current path
Pick-up time
20 ms typ. (K1, K2 - for UN automatic mode)
20 ms typ. (at Uₑ in automatic mode)
20 ms typ. (K1, K2 - for UN manual operation)
20 ms typ. (at Uₑ in manual mode)
Lifespan, mechanical
10,000,000 Operations
Input
∞ ms, Simultaneity for inputs 1/2
Recovery time
1000 ms
Inrush current
0.025 - 6 A (N/O)
0.025 - 3 A (N/C)
Model
Expansion device
Safety type (IEC 61496-1)
None
Vibration resistance
10 - 150 Hz, Amplitude: 0.15 mm, Acceleration: 2 g, (IEC/EN 60068-2-6)
Safety parameter (EN ISO 13849-1)
300,000 switching cycles, B10d
PL d, Performance level
Cat. 3, Category
Terminal capacity
1 x (0.2 – 2.5) mm², solid
1 x (0.25 – 2.5) mm², flexible with ferrule
2 x (0.25 – 1) mm², flexible with ferrule
24 - 12 AWG, solid or stranded
2 x (0.2 – 1) mm², solid
Rated control supply voltage (Us) at AC, 60 Hz - min
20.4 V
Rated control supply voltage (Us) at DC - max
24 V
Rated control supply voltage (Us) at DC - min
0 V
Rated insulation voltage (Ui)
250 V
Rated operational current for specified heat dissipation (In)
0 A
Release-delay - max
0 s
Release-delay - min
0 s
Static heat dissipation, non-current-dependent Pvs
4.52 W
Stripping length (main cable)
7 mm
Switching voltage
250 V
Product category
Electronic safety relays
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
SIL (IEC 61508)
3
Power loss
Normally 4.52 W
Power supply circuit
2 W (DC operated)
Prooftest
67 Months (Low Demand)
240 Months (High Demand)
Quadratic summation current
50 A² (ITH² = I1² + I2² + I3² + I4²)
Rated operational voltage
24 V DC (power supply)
230 V AC
Safety parameter (IEC 62061)
SIL 3, Safety integrity level, In accordance with IEC 61508
SILCL 3, Safety integrity level claim limit
SILCL 2, Safety integrity level claim limit
SIL 2, Safety integrity level, In accordance with IEC 61508
13.5 x 10-10, PFHd, Probability of failure per hour
Cat. 3, Category
Uninterrupted current
3 A N/C, Limiting continuous current
6 A N/O, Limiting continuous current
Short-circuit protection
Fuse 4 A gL/gG (Signal current paths), For output circuits, External
Fuse 10 A gL/gG (Enable current paths), For output circuits, External
Stop category (IEC 60204)
1
Switching capacity
3 A at 3600 O/h, AC-15 at 230 V, Outputs
In accordance with IEC 60947-5-1, Outputs
0.4 W
3 A at 3600 O/h, DC-13 at 24 V, Outputs
Switching frequency
Max. 0.5 Hz, Input data
Power consumption
4.52 W
Control voltage 1 - min
24 V
Control voltage 1 - max
24 V
Control voltage 2 - min
24 V
Control voltage 2 - max
24 V
Control voltage 1 type
DC
Control voltage 2 type
DC
Voltage type of supply voltage
DC
Voltage type of operating voltage
DC
Rated switch current
6 A
Supply voltage at AC, 50 Hz - min
0 V
Supply voltage at AC, 50 Hz - max
0 V
Supply voltage at AC, 60 Hz - min
0 V
Supply voltage at AC, 60 Hz - max
0 V
Supply voltage at DC - min
24 V
Supply voltage at DC - max
24 V
Operating voltage at AC, 50 Hz - min
0 V
Operating voltage at AC, 50 Hz - max
0 V
Operating voltage at AC, 60 Hz - min
0 V
Operating voltage at AC, 60 Hz - max
0 V
Operating voltage at DC - min
24 V
Operating voltage at DC - max
24 V

导出产品规格