照片为代表
Download
Eaton Moeller® series EMS DOL starter, 24 V DC, 1,5 - 6,5 (AC-53a), 9 (AC-51) A, Push in terminals, PTB 13 ATEX 3003
Product Name |
Eaton Moeller® series EMS DOL starter
|
Catalog Number |
170100
|
Product Length/Depth |
160 mm
|
Product Height |
60 mm
|
Product Width |
155 mm
|
Product Weight |
0.3 kg
|
Certifications |
IEC/EN 60947-4-2
IEC/EN 61000-4-3 UL 508 UL Category Control No.: NLDX, NLDX7 CSA-C22.2 No. 14 UL File No.: E29096 IEC/EN 60947-5 IEC/EN 61000-4-2, Level 3 PTB 13 ATEX 3003 UL Certified by UL for use in Canada UL508 CE UL report applies to both US and Canada |
Type |
DOL starter (complete device)
|
Air discharge |
8 kV
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Operating frequency |
7200 Operations/h (pulse pause time 50:50)
|
Pollution degree |
2
|
Class |
CLASS 10 A (Ir > 4 A)
CLASS 10 CLASS 10 (Ir ≤ 4 A) |
Burst impulse |
According to IEC/EN 61000-4-4, level 3
2 kV |
Lifespan, electrical |
30,000,000 Operations
|
Connection to SmartWire-DT |
No
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Model |
Direct starter
|
Explosion safety category for dust |
ATEX dust-ex-protection, II (2) G [Ex e] [Ex d] [Ex px]
ATEX dust-ex-protection, II (2) D [Ex t] [Ex p] |
Environmental conditions |
Condensation: prevent with appropriate measures
Designed for operation in industrial environments. The use in residential environments could cause electrical interference so that addition suppression must be planned. |
Electrical connection type of main circuit |
Spring clamp connection
|
Voltage type |
DC
|
Mounting position |
Motor feeder at bottom
Vertical |
Mounting method |
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
Contact discharge |
6 kV
|
Overvoltage category |
III
|
Connection |
Push in terminals
|
Supply voltage |
A1 - A2: 24 V DC (-20 - +25 %), UAUX, Control section, Input data
|
Basic insulation |
500 V AC, between feedback signal output and switch voltage according to IEC/EN60947-1
500 V AC, between supply voltage, control voltage and switch voltage according to IEC/EN60947-1 |
Functions |
Temperature compensated overload protection
External reset possible Motor protection DOL starting |
Surge rating |
1 kV, symmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC 2 kV, asymmetrical, power pulses (Surge), EMC |
Terminal capacity |
1 x (0.75 - 2.5) mm², solid
2 x (0.75 - 1.5) mm², flexible, with twin ferrule 2 x (0.75 - 2.5) mm², flexible with ferrule Minimum length 10 mm. |
Terminal capacity (AWG) |
1 x (20 - 14), solid
1 x (20 - 14), flexible with ferrule 2 x (20 - 16), flexible with twin ferrule |
Electromagnetic fields |
10 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
10 V/m at 800 - 1000 MHz (according to IEC EN 61000-4-3) 3 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3) |
Overload release current setting - min |
1.5 A
|
Rated conditional short-circuit current (Iq), type 2, 230 V |
0 A
|
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V |
0 A
|
Rated conditional short-circuit current, type 1, 480 Y/277 V |
0 A
|
Rated conditional short-circuit current, type 1, 600 Y/347 V |
0 A
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V |
3 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
6.5 A
|
Immunity to line-conducted interference |
10 V (according to IEC/EN 61000-4-6)
|
Radio interference class |
Class A (EN 61000-6-3, emitted interference, radiated)
Class A (EN 55011, emitted interference, line-conducted) |
Pick-up current |
45 A (stall protection)
|
Safe isolation |
300 V AC; Between supply, control, and switching voltages; According to EN50178
300 V AC, Between feedback signal output and switch voltage, According to EN 50178 500 V AC, Between feedback signal output and switch voltage, According to EN 50178 500 V AC; Between supply, control, and switching voltages; According to EN50178 |
Pick-up time |
2 s (stall protection)
|
Residual ripple |
≤ 5 % (input voltage)
|
Recovery time |
2 min (manual startup)
20 min (automatic restart) |
Rated operational current (Ie) |
9 A
|
Rated operational current (Ie) at AC-51 |
9 A
|
Rated operational current (Ie) at AC-53A - max |
6.5 A
|
Rated operational current (Ie) at AC-53A - min |
1.2 A
|
Rated operational current (Ie) at DC-13, 24 V |
2 A
|
Rated operational current for specified heat dissipation (In) |
6.5 A
|
Rated operational voltage |
250 V AC/DC
42 - 550 V |
Safety parameter (EN ISO 13849-1) |
316 years; MTTFD
|
Safety parameter (IEC 62061) |
SIL: 2
Λdu [FIT]: 47.2 97.9 %, SFF Λsd [FIT]: 0 Λsu [FIT]: 1550 86,9 %, DC Λdd [FIT]: 314 |
Switching level |
19.2 - 30 V DC, Switching level "High", Actuating circuit (ON, L, R)
-3 - 9.6 V DC, Switching level "Low", Actuating circuit (ON, L, R) < 5 V DC, Switching level "confirm Off", Actuating circuit (ON, L, R) |
Short-circuit protection rating |
15 kA, 415 V AC: PKM0-6,3, Short-circuit protective device, Type “1” coordination, Main conducting paths
50 kA, 415 V AC: PKM0-4, Short-circuit protective device, Type “1” coordination, Main conducting paths 50 kA, 500 V AC: Fuse 16 A gG/gL, Short-circuit protective device, Type “1” coordination, Main conducting paths |
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-25 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Equipment heat dissipation, current-dependent Pvid |
6.3 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
2.1 W
|
Number of auxiliary contacts (normally closed contacts) |
1
|
Number of auxiliary contacts (normally open contacts) |
1
|
Number of command positions |
0
|
Number of contacts (change-over contacts) |
1
|
Number of pilot lights |
4
|
Overload release current setting - max |
9 A
|
Rated operational power at AC-3, 220/230 V, 50 Hz |
1.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
3 kW
|
Rated operational power at AC-53A, 380/400 V, 50 Hz |
3 kW
|
Rated power at 460 V, 60 Hz, 3-phase |
2.2 kW
|
Rated power at 575 V, 60 Hz, 3-phase |
0 kW
|
Static heat dissipation, non-current-dependent Pvs |
1 W
|
Product category |
Electronic motor starter
|
Balance monitoring |
If ≥ 67 %, pick-up time of 1.8 s, Magnitude Imax > Irated ((Imax - Imin)/Imax)
If ≥ 33 %, pick-up time of 120 s, Magnitude Imax > Irated ((Imax - Imin)/Imax) If ≥ 67 %, pick-up time of 1.8 s, Magnitude Imax < Irated ((Imax - Imin)/Imax) If ≥ 33 %, pick-up time of 120 s, Magnitude Imax < Irated ((Imax - Imin)/Imax) |
Coordination class (IEC 60947-4-3) |
Class 1
|
Degree of protection |
IP20
IP20 (according to IEC/EN 60529, EN 50178, VBG 4) |
Electrical connection type for auxiliary- and control-current circuit |
Spring clamp connection
|
Input current |
5 mA (Actuating circuit - ON, L, R)
40 mA (without feedback signal) |