Eaton XC XC303 modular PLC, small PLC, programmable CODESYS 3, SD Slot, Ethernet, CAN
Product Name |
Eaton XC Modular PLC
|
Catalog Number |
191082
|
Product Length/Depth |
108 mm
|
Product Height |
65 mm
|
Product Width |
85 mm
|
Product Weight |
0.28 kg
|
Certifications |
CE
EN 61131 UL listed EAC UL File No.: E205091 cULus Listed |
Catalog Notes |
Protective devices must be installed directly at the inductive load in order to prevent interference.
|
Type |
Modular PLC XC300
|
Features |
Short-circuit protection (digital outputs)
|
Air discharge |
8 kV/4 kV, Air/contact discharge, ESD
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
2
|
Burst impulse |
1 kV, Signal cable
2 kV, Supply cable |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2 |
Air pressure |
795 - 1080 hPa (operation)
|
Explosion safety category for dust |
None
|
Environmental conditions |
Condensation: prevent with appropriate measures
|
Explosion safety category for gas |
None
|
Output current |
0.5 A
|
Mounting method |
Rail mounting possible
|
Voltage type |
DC
|
Mounting position |
Vertical (on horizontal top-hat rail)
|
Memory capacity |
512,000 kByte
|
Number of channels |
4, Digital Outputs
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-20 °C
|
Ambient storage temperature - max |
80 °C
|
Ambient storage temperature - min |
-40 °C
|
Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
0
|
Overvoltage category |
II
|
Surge rating |
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
1 kV, Signal cable, unbalanced, EMC |
Emitted interference |
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency)
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency) |
Terminal capacity (AWG) |
24 - 16
|
Electromagnetic fields |
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
Load current |
Max. 6 A per 1.5 mm² (cross-sectional area)
|
Number of inputs (analog) |
0
|
Connection type |
Push-in spring-cage terminal, Connection design in TOP direction
|
Radiated RFI |
10 V
|
Memory type |
RAM
|
Number of outputs (digital) |
0
|
Relative humidity |
< 95 % (non-condensing)
|
Degree of protection |
IP20
|
Number of relay outputs |
0
|
Delay time |
200 µs, Digital outputs, Delay on signal change and resistive load, from Low to High signal
200 µs, Digital outputs, Delay on signal change and resistive load, from High to Low signal |
Protocol |
MODBUS
CAN Other bus systems TCP/IP EtherNet/IP |
Digital outputs |
Note: Protective devices must be installed directly at the inductive load in order to prevent interference.
|
Rated operational current (Ie) |
2.8 A (supply input)
|
Heat dissipation |
0.05 W (Digital inputs according to EN61131-2 Type 1, per active channel)
0.1 W (Digital outputs, internal, per active channel) |
Functions |
Redundancy
Additional program memory possible |
Gauge pin |
A1 (according to IEC/EN 60947-1)
|
Vibration resistance |
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
|
Input current |
≥ 2.3 mA (Digital inputs, high level)
2 mA (Ie) ≤ 1.1 mA (Digital inputs, low level) |
Input delay |
300 µs (rising edge)
300 µs (falling edge) |
Shock resistance |
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
|
Input voltage |
15 - 30 V (Digital inputs, high level)
24 V DC (Digital inputs) 0 - 5 V (Digital inputs, low level) |
Number of time switches - max |
1000
|
Processing time |
0.001 ms
|
Static heat dissipation, non-current-dependent Pvs |
8 W
|
Stripping length (main cable) |
10 mm
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
30 VDC
|
Supply voltage at DC - min |
18 VDC
|
Heat dissipation details |
The max. heat dissipation is specified as the maximum power produced inside the device's housing.
|
Insulating material group |
I
|
Terminal capacity (flexible) |
0.2 - 1.5 mm², H 07V-K
|
System accessory |
Yes
|
Model |
Modular
|
Utilization factor |
100 % (Ʃ IAmax = 2A)
|
Potential isolation |
Between Digital inputs: no
Between Digital outputs: no |
Number of inputs (digital) |
0
|
Voltage dips |
Voltage dips: 10 ms/Voltage fluctuations: Yes
|
Rated operational voltage |
24 V
160 V (terminations) |
Terminal capacity |
0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
|
Terminal capacity (flexible with ferrule) |
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25 - 1.5 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
Terminal capacity (solid) |
0.2 - 1.5 mm², H07V-U
|